Configuration – Lenze EVF9383 User Manual

Page 133

Advertising
background image

Configuration

2−125

l

EDSVF9383V−EXT EN 2.0

t

U G

t 1

t 2

t

n

0

0

M F A I L - D C - S E T

t 3

Q
R

S

T

Fig. 2−98

Schematic representation with different brake torques



Switch−off threshold OU

‚

Switch−on threshold for brake unit

ƒ

Switch−off threshold LU

„

Threshold CMP2−OUT

t = t1 Mains failure
t = t2 Zero speed with higher brake torque (short adjustment time)
t = t3 Drive reaches the LU switch−off threshold with lower brake torque (high adjustment time), without reaching zero

speed

t > t3 Drive is no longer under control (is braked by friction)

2.4.41.3

Restart protection

The integrated restart protection is to avoid a restart in the lower speed range, after the supply voltage
was interrupted for a short time only (mains recovery before the drive has come to standstill).

l

Establish the restart protection. (

¶ 2−118, point 6.)

l

In C0472/18, enter the threshold in [%] of n

max

(C0011) below which no automatic start is

wanted after mains recovery.

– If the speed at mains recovery < threshold in C0472/18, the drive will still be braked under

control. This function can only be ended by MFAIL−RESET = HIGH.

– If the speed at mains recovery > threshold in C0472/18, the drive accelerates to its setpoint

along the set ramps.

l

This function is deactivated by:

– C0472/18 = 0 % or

– C0975 = 1000 (FIXED0% to MFAIL−THRESHLD)

l

A reset is made by MFAIL−RESET = HIGH:

– A reset is required after every mains (re)connection

– The reset is shown by MFAIL−STATUS = HIGH, when MFAIL−FAULT = LOW.