Configuration – Lenze EVF9383 User Manual

Page 93

Advertising
background image

Configuration

2−85

l

EDSVF9383V−EXT EN 2.0

2.4.22.5

TRIP−RESET

TRIP−RESET resets an active trip once the cause of fault has been eliminated. If the cause of fault
is still active, there is no reaction.

l

The function is activated via four inputs:

– Control word CAN−CTRL.B11 from CAN−IN1

– Control word AIF−CTRL.B11 from AIF−IN

– Control word C0135.B11

– Free input DCTRL−TRIP−RESET

l

All inputs are linked by an OR−operation.

l

The function can only be performed by a LOW−HIGH edge of the signal resulting from the OR
operation.

Tip!

If one of the inputs is set to HIGH, no LOW−HIGH edge can occur at the resulting signal.

2.4.22.6

Changing the parameter set (PAR)

The controller loads and uses the selected parameter set.

l

The parameter set to be loaded is selected via the inputs DCTRL−PAR*1 and DCTRL−PAR*2.
The inputs are binary coded (1 of 4).

PAR*2

PAR*1

Selected parameter set

0

0

Parameter set 1

0

1

Parameter set 2

1

0

Parameter set 3

1

1

Parameter set 4

l

With a LOW−HIGH − signal at the input DCTRL−PAR−LOAD the controller changes to the
selected parameter set.

l

The parameter set can be changed only if the controlled inhibit is activated. (

¶ 2−84)

Tip!

If the parameter set to be loaded via terminal X5/Ex is selected before connecting the supply voltage,
the LOW−HIGH signal at the input DCTRL−PAR−LOAD is not necessary. In this case, the controller
loads automatically the selected parameter set.

l

The controller is not ready for approx. 1 s. DCTRL− RDY shows LOW during this time.