Motor phase failure detection (MLP)

Purpose

Motor phase monitoring.

MLP1

Fig. 2−99

Motor phase failure detection (MLP1)

Code

LCD

Possible settings

IMPORTANT

Lenze

Selection

C0597 MONIT LP1

3

0

Trip

2

Warning

3

Off

Conf. LP1
Configuration of motor phase failure
monitoring

C0599 LIMIT LP 1

5.0

1.0

{0.1}

10.0 Current limit LP1

Current limit for motor phase failure
monitoring

Function

For detailed descriptions of the monitorings / error messages, please see the chapter
"Troubleshooting and fault elimination" in the System Manual.

The function block MLP1 must be entered into the processing table, if the motor phase failure
detection shall be used.