Limitation (lim), Configuration, 38 limitation (lim) – Lenze EVF9383 User Manual

Page 120

Advertising
background image

Configuration

2−112

l

EDSVF9383V−EXT EN 2.0

2.4.38

Limitation (LIM)

This FB limits the input signal to an adjustable range.

LIM1

LIM1−OUT

LIM1−IN

C0633

C0630

C0631

C0632

Fig. 2−91

Limitation (LIM1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

LIM1−IN1

a

C0633

dec [%]

C0632

1

1000

LIM1−OUT

a

Function

l

If the input signal exceeds the upper limit (C0630), the upper limit is effective.

l

If the input signal falls below the lower limit (C0631), the lower limit is effective.

Tip!

The lower limit (C0631) must be smaller than the upper limit (C0630).

Advertising
This manual is related to the following products: