Torque control (c0005 = 4000), Configuration, Basic configuration – Lenze EVF9383 User Manual

Page 23

Advertising
background image

Configuration

Basic configuration

2−15

l

EDSVF9383V−EXT EN 2.0

2.2.6

Torque control (C0005 = 4000)

Configuration C0005 = 4000 is designed for drive control via a torque setpoint.

The setpoint is selected via the analog input X6/2. The torque direction results from the sign of the
setpoint and the control of the digital inputs X5/E1 and X5/E2. The maximum permissible speed is
selected via the analog input X6/1.

Short setup

The "Short setup" menu contains the following codes. In the "Short setup" menu of the XT keypad
and "Global Drive Control", the codes are listed in the following order.

Code

Explanation

Lenze setting

C0005

Selection of the basic configuration

4000

C0010

Minimum speed

Reference value for the absolute and relative setpoint selection for the
acceleration and deceleration times

0 rpm

C0011

Maximum speed

3000 rpm

C0012

Acceleration time T

ir

of the main setpoint

5.00 s

C0013

Deceleration time T

if

of the main setpoint

5.00 s

C0034

Voltage / current range for analog signals at the input X6/1, X6/2

0

C0039/1

JOG setpoints for the speed setpoint conditioning, function block NSET

1500 rpm

C0105

Quick stop deceleration time

5.00 s

C0909

Speed limitation, function block MCTRL

1

C0026/1

Offset of AIN1 (X6/1, X6/2)

0.00 %

C0026/2

Offset of AIN2 (X6/3, X6/4)

0.00 %

C0027/1

Gain AIN1 (X6/1, X6/2)

100.00 %

C0027/2

Gain AIN2 (X6/3, X6/4)

100.00 %

C0006

Selection of the operating mode for the motor control

5

C0022

I

max

limit in motor mode

depends on the
controller

C0023

I

max

limit in generator mode

depends on the
controller

C0025

Speed feedback

1

C0070

Speed controller gain

10.0

C0071

Adjustment time of speed controller

50 ms

C0074

Limitation of the speed controller

10.00 %

C0898

Torque limitation in the field weakening range, function block MCTRL

0

C0472/3

Free control code for analog signals

100.00 %

C0017

Q

min

switching threshold (FCODE)

50 rpm