Configuration

Basic configuration

2−6

l

EDSVF9383V−EXT EN 2.0

2.2.2

Control

The controller can be controlled via terminals (X5 and X6), a fieldbus module at X1, the system bus
(X4) or by a combination of these.

Under the fourth digit of code C0005 you can select the interface used to control the controller.

Example: C0005 = 1005

This configuration corresponds to speed control with control via the system bus (CAN).

If you want to control further FB inputs via an interface, you first have to

l

assign "control objects" to the FB inputs to be controlled depending on the interface that is
used (see chapter 2.3.3):

– Free control codes

for control via LECOM A/B/LI (RS232, RS485 or optical fibre interface) or operating module.

– AIF objects

for control, e.g. via INTERBUS or PROFIBUS−DP.

– CAN objects

for control via system bus.

l

After this, the inputs can be controlled via these codes or input objects by accessing them via
the interface.

Example: Distributing control to terminals and RS232:

The main speed setpoint in configuration C0005=1000 shall be controlled via LECOM A/B/LI. All
other inputs continue to be controlled via terminals.

1. Select C0780 via LECOM:

– C0780 is the configuration code for the main setpoint NSET−N in the function block "Speed

setpoint conditioning" (NSET).

2. Assign a free control code via the selection number:

– E.g. 19515 (control code C0141).

The main speed setpoint is now controlled via C0141.