Configuration – Lenze EVF9383 User Manual

Page 160

Advertising
background image

Configuration

2−152

l

EDSVF9383V−EXT EN 2.0

2.4.52.1

Ramp function generator

The maximum speed of change with which the output signal can follow the input signal, is
parameterized via the acceleration and deceleration time of the ramp function generator. They refer
to a change of the output signal from 0 to 100%. The times to be set T

ir

and T

if

are to be calculated

as follows:

100 %

0

tir

tif

Tir

Tif

t

RFG1−OUT

[%]

w1

w2

T

ir

+ t

ir

@ 100 %

w2

* w1

T

if

+ t

if

@ 100 %

w2

* w1

Fig. 2−130

Acceleration and deceleration times of the ramp function generator

Here, t

ir

and t

if

are the desired times for the change between w1 and w2. You can set the calculated

value under C0671 (T

ir

) and C0672 (T

if

).

2.4.52.2

Load ramp function generator

You can initialize the ramp function generator with defined values via the inputs RFG1−SET and
RFG1−LOAD.

l

As long as RFG1−LOAD = HIGH, the value at RFG1−SET is switched to RFG1−OUT.

l

If the RFG1−LOAD = LOW, the ramp function generator accelerates from this value to its input
value at REG1−IN via the set T

i

times.