Configuration

Use of funktion blocks

2−37

l

EDSVF9383V−EXT EN 2.0

Building up connections

1. Determine the signal source for ARIT2−IN1:

– Use the arrow keys and go to the code level.

– Use

z or y to select C0601/1.

– Press PRG to go to the parameter level.

– Use

z or y to select the output AIN2−OUT (selection number 55).

– Confirm with SH + PRG.

– Press PRG to go back to the code level.

2. Determine the signal source for ARIT2−IN2:

– Use

z to select C0601/2.

– Press PRG to go to the parameter level.

– Use

z or y to select the output AIN2−OUT (selection number 55).

– Confirm with SH + PRG.

– Press PRG to go back to the code level.

3. Parameterise ARIT2:

– Use

y to select C0600.

– Press PRG to go to the parameter level.

– Select multiplication (selection number 3).

– Confirm with SH + PRG.

– Press PRG to go back to the code level.

4. Determine the signal source for AOUT1:

– Use

y to select C0431.

– Press PRG to go to the parameter level.

– Select output ARIT2−OUT (selection number 5505).

– Confirm with SH + PRG.

– Press PRG to go back to the code level.

5. Enter function block ARIT2 into the processing table:

– Use

z to select C0465 and subcode 8.

– Press PRG to go to the parameter level.

– Enter function block ARIT2 (selection number 5505).

– Confirm with SH + PRG.

– Press PRG to go back to the code level.

– This determines the order of FB processing.