Configuration

2−149

l

EDSVF9383V−EXT EN 2.0

Load ramp generator (only PCTRL2)

A jerk−free acting of the process controller is possible only when the setpoint ramp generator has
previously been loaded with the actual value.

l

PCTRL2−RFG−LOAD = HIGH activates the function.

l

The start value (e.g. the actual value) is entered via PCTRL2−RFG−SET.

2.4.50.3

Value range of the output signal

Range of the process controller

PCTRL1

PCTRL2

Limitation

Bipolar (default setting)

C0337 = 0

C1335 = 0

Limits the output value to ±100 %

Unipolar

C0337 = 1

C1335 = 1

Limits the output value to 0 ... +100 %

2.4.50.4

Evaluating the output signal

After the limitation, the output signal is evaluated.

PCTRL1

You can enter the influence of the process controller via PCTRL1−INFLU.

l

With PCTRL1−INFLU = 100 %, the output signal of the controller is output unchanged. The
influence changes in relation to the value at PCTRL1−INFLU.

PCTRL2

The overlay function of the process controller can be slowly activated or deactivated using an internal
ramp generator.

l

The influence of the process controller is entered via PCTRL2−INFL.

l

The influence is activated with PCTRL2−OVERLAY = HIGH.

l

The influence is deactivated with PCTRL2−OVERLAY = LOW.

l

Ramps for activation and deactivation:

– C1336 = Acceleration time T

ir

– C1337 = Deceleration time T

if

2.4.50.5

Deactivating the process controller

l

The process controller is deactivated using PCTRLx−INACT = HIGH.

– PCTRLx−OUT is set to zero.

– The I−component is set to zero.

– The ramp generator is set to zero.