2.4.45

Blocking frequencies (NLIM)

This FB blocks signals in max. three speed ranges which can be defined. The output signal skips the
defined ranges. If you use the output signal as setpoint speed, the motor only passes the blocked
ranges.

NLIM1

NLIM1−OUT

NLIM1−IN

C0511

C0038/5

C0510

C0038/3

C0038/1

C0038/6

C0038/4

C0038/2

Fig. 2−104

Blocking frequencies (NLIM1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

NLIM1−IN

a

C0511

dec [%]

C0510

1

1000

NLIM1−OUT

a

Function

A blocked speed range is activated by entering a lower and an upper speed limit.

The output signal remains at the lower limit of the block range until the input signal has over− or
undershot the blocked speed range.

Code

Choice

Function

C0038/1

0 {1

rpm}

36000

0 = Function not active

Blocked speed range 1

defines the lower limit

C0038/2

defines the upper limit

C0038/3

Blocked speed range 2

defines the lower limit

C0038/4

defines the upper limit

C0038/5

Blocked speed range 3

defines the lower limit

C0038/6

defines the upper limit

-C0038/2

C0011

C0038/3

C0011

-C0038/1

C0011

C0038/4

C0011

NLIM1-IN

NLIM1-OUT





‚

‚

Fig. 2−105

Representation of the upper and lower limits of the blocked speed ranges
 Blocked speed range 1
‚ Blocked speed range 2