Configuration, Stop – Lenze EVF9383 User Manual

Page 130

Advertising
background image

Configuration

2−122

l

EDSVF9383V−EXT EN 2.0

4. Select the threshold for the mains failure detection under C0472/20. The selection depends on

the setting under C0173.

– Set the threshold approx. 50 V above the switch−off threshold LU (example for C0173 = 0.1;

C0472/20 = 33.5 % = 335 V).

9300 vector

UG thresholds

EVF9321 ... EVF93
33

Mains voltage range

C0173

Switch−off

threshold LU

Switch−on

threshold LU

Switch−off

threshold OU

Switch−on

threshold OU

< 400 V

Operation with/without brake chopper

0

285 V

430 V

770 V

755 V

400 V

Operation with/without brake chopper

1

*

285 V

430 V

770 V

755 V

460 V

Operation with/without brake chopper

2

328 V

473 V

770 V

755 V

480 V

Operation without brake chopper

3

342 V

487 V

770 V

755 V

480 V

Operation with brake chopper

4

342 V

487 V

800 V

785 V

9300 vector

UG thresholds

EVF9335 ... EVF93
83

Mains voltage range

C0173

Switch−off

threshold LU

Switch−on

threshold LU

Switch−off

threshold OU

Switch−on

threshold OU

EVF93xx−ExV210
EVF93xx−ExV240
EVF93xx−ExV270
EVF93xx−ExV300

< 400 V

Operation with or without brake transistor

0

285 V

430 V

770 V

755 V

400 V

Operation with or without brake transistor

1

*

285 V

430 V

770 V

755 V

460 V

Operation with or without brake transistor

2

328 V

473 V

770 V

755 V

480 V

Operation without brake transistor

3

342 V

487 V

770 V

755 V

480 V

Operation with brake transistor

4

342 V

487 V

800 V

785 V

500 V

Operation with or without brake transistor

5

342 V

487 V

900 V

885 V

EVF93xx−Ex
EVF93xx−ExV060
EVF93xx−ExV110

400 V

Operation with or without brake transistor

Only

display

285 V

430 V

700 V

685 V

*

Lenze setting

Stop!

This setpoint must be below the threshold of any brake unit which may be connected. If a connected
brake unit is activated, the drive is braked with the maximum possible torque (I

max

). The desired

operating behaviour is lost.

5. Set the setpoint to which the DC−bus voltage is to be controlled:

– Set the setpoint to approx. 700 V (C0472/18 = 70 %).