Configuration – Lenze EVF9383 User Manual

Page 75

Advertising
background image

Configuration

2−67

l

EDSVF9383V−EXT EN 2.0

Function procedure

1. When pulse inhibit (IMP) by controller inhibit or a fault (LU, OU, ...), BRK−OUT changes

immediately to HIGH.

– The drive is then braked by its mechanical brake.

2. When pulse inhibit is reset (DCTRL−CINH = LOW) before the actual speed has fallen below the

threshold BRK−Nx, BRK−OUT changes immediately to LOW (possible only with incremental
encoder).

– The drive synchronizes itself to the momentary speed and follows its setpoint.

– The drive starts once the threshold was undershot. (

¶ 2−65)

t

t

BRK1−SET

MCTRL−NSET2

BRK1−OUT

BRK1−CINH

MCTRL−MACT

MCTRL−MACT = C0244

t

t

BRK1−M−STORE

t

BRK1−QSP

|BRK1−Nx|

t

t

C0195

C0196

Fig. 2−49

Stopping and starting switching cycle