Output of digital status signals (stat), Configuration, 57 output of digital status signals (stat) – Lenze EVF9383 User Manual

Page 167

Advertising
background image

Configuration

2−159

l

EDSVF9383V−EXT EN 2.0

2.4.57

Output of digital status signals (STAT)

The FB accepts digital signals of the function blocks and the status of the controller and passes them
on to C0150 and to the FB AIF−OUT and CAN−OUT1.

C0156/1 STAT.B0

STAT.B2
STAT.B3

STAT.B4

STAT.B5

STAT.B14

STAT.B15

DCTRL−IMP

STAT

DCTRL−WARN

DCTRL−MESS

DCTRL−NACT=0

C0156/2

C0156/3

C0156/4

C0156/5

DCTRL−STAT*1

DCTRL−STAT*2

DCTRL−STAT*4

DCTRL−STAT*8

0

1

2

3

4

5

6

8

9

DCTRL−CINH

7

10

11

12

13

14

15

C0156/6

C0156/7

AIF−
Status word

C0150

CAN1−
Status word

Fig. 2−138

Output of digital status signals (STAT)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

STAT.B0

d

bin

C0156/1

2

2000

STAT.B2

d

bin

C0156/2

2

5002

STAT.B3

d

bin

C0156/3

2

5003

STAT.B4

d

bin

C0156/4

2

5050

STAT.B5

d

bin

C0156/5

2

10650

STAT.B14

d

bin

C0156/6

2

505

STAT.B15

d

bin

C0156/7

2

500

Function

The status word consists of some linked (DCTRL−xxxx−) and some freely linkable signal inputs
(STAT.Bx).

l

Digital signal sources can be freely assigned to the inputs STAT.Bx.

l

The corresponding bit in the data word is marked with STAT.Bx (e.g. STAT.B0 for the least
significant bit).

l

The status word is transferred to code C0150 and to the function blocks AIF−OUT, CAN−OUT1,
CAN−OUT2, and CAN−OUT1.

l

The inputs with the name DCTRL−xxxx are directly accepted from the function block DCTRL.
(

¶ 2−82)

Advertising