Configuration – Lenze EVF9383 User Manual

Page 138

Advertising
background image

Configuration

2−130

l

EDSVF9383V−EXT EN 2.0

2.4.44.2

Deactivation of the motor potentiometer

You can deactivate the function of the motor potentiometer using the input MPOT1−INACT.

l

The motor potentiometer function is deactivated with MPOT1−INACT = HIGH.

l

The input MPOT1−INACT has priority over the inputs MPOT1−UP and MPOT1−DOWN.

l

When the function is deactivated, the output signal at MPOT1−OUT follows the function set
under C0264. You can set the following functions under C0264:

C0264

Meaning

0

No further action; the output MPOT1−OUT keeps its value

1

The motor potentiometer returns to 0 % with the corresponding Ti time

2

The motor potentiometer approaches its lower limit (C0261) with the corresponding deceleration time

3

The motor potentiometer immediately changes its output to 0 % (important for emergency stop function)

4

The motor potentiometer immediately changes its output to the lower limit (C02619

5

The motor potentiometer approaches its upper limit (C0260) with the corresponding Ti time

If the deactivation of the motor potentiometer is cancelled with MPOT1−INACT = LOW, the
subsequent function depends on

l

the momentary output signal,

l

the set limits (C0261: lower limit, C0260: upper limit),

l

the control signals MPOT1−UP and MPOT1−DOWN.

If the output value is out of the limits, the output signal approaches the next limit with the suitable T

i

time (C0262: acceleration time T

ir

, C0263: deceleration time T

if

). This function is independent of the

control inputs MPOT1−UP and MPOT1−DOWN

If the output value is within the limits, the output signal follows the selected control function
MPOT1−UP, MPOT1−DOWN or no action.

Tif

Tir

Tir

Tif

MPOT1−UP

MPOT1−DOWN

C0260

C0261

0

MPOT1−OUT

Tif

MPOT1−INACT

Fig. 2−103

Deactivation of the motor pot via the input MPOT1−INACT