Process controller (pctrl), Configuration, 50 process controller (pctrl) – Lenze EVF9383 User Manual

Page 153: You can adapt the gain in the fb pctrl1

Advertising
background image

Configuration

2−145

l

EDSVF9383V−EXT EN 2.0

2.4.50

Process controller (PCTRL)

You can use these FBs for the control of state variables such as pressure, level, dancer position, etc.

Setpoint and actual value are sent to the process controller via the corresponding inputs and
processed according to the selected control algorithm (PID−, PI− or P−algorithm).

l

You can adapt the gain in the FB PCTRL1.

l

The FB PCTRL2 is optimal for control circuits which must be activated or deactivated online.

1

0

2

V p

V p 2

V p 3

V p 2

V p

+
-

C 0 2 2 2

s o l l 1

s o l l 2

C 0 3 2 9

C 0 2 2 3

C 0 2 2 4

P C T R L 1 - S E T

C 0 8 0 8 / 1

P C T R L 1 - I N A C T C 0 8 0 8 / 2

C 0 3 3 3

C 0 3 3 2

3

2

P C T R L 1 - O U T

C 0 8 0 8 / 4

C 0 3 3 7

C 0 8 0 9 / 1

P C T R L 1 - I N F L U

C 0 8 0 8 / 3

P C T R L 1 - A C T

P C T R L 1 - I - O F F

C 0 8 0 9 / 2

3

C 0 8 0 3

C 0 8 0 0

C 0 8 0 1

C 0 8 0 4

C 0 8 0 5

C 0 8 0 2

P C T R L 1 - A D A P T

C 0 3 3 6

P C T R L 1

± 1 0 0 %

C 0 2 2 2

C 0 3 2 5
C 0 2 2 2
C 0 3 2 5
C 0 3 2 6

C 0 3 2 7

C 0 3 2 8

R E S E T

Fig. 2−121

Process controller (PCTRL1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

PCTRL1−SET

a

C0808/1

dec [%]

C0800

1

1000

Input for process setpoint. Possible value
range: ±200 %. The time of step−change
signals can be decelerated via the ramp
generator (C0332 for the acceleration time;
C0333 for the deceleration time).

PCTRL1−ACT

a

C0808/2

dec [%]

C0801

1

1000

Input for actual value; value range

200 %

PCTRL1−INFLU

a

C0808/3

dec [%]

C0802

1

1000

Evaluation (influence) of the output signal;
value range ±200 %

PCTRL1−ADAPT

a

C0808/4

dec [%]

C0803

1

1000

Changing the gain V

p

;

Value range ±200 % (online)

PCTRL1−INACT

d

C0809/1

bin

C0804

2

1000

HIGH = Inactivation of the process
controller (online)

PCTRL1−I−OFF

d

C0809/2

bin

C0805

2

1000

HIGH = switch off I component (online)
LOW = switch off I component (online)

PCTRL1−OUT

a

Advertising