2−74

l

EDSVF9383V−EXT EN 2.0

2.4.17

Conversion (CONV)

These FBs convert analog signals or convert signals into another signal type. The conversion factor
as numerator and denominator is calculated using residual value processing.

CONV1

CONV1

CONV1−OUT

CONV1−IN

C0943

C0942

C0940
C0941

Fig. 2−57

Conversion (CONV1)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

CONV1−IN

a

C0943

dec [%]

C0942

1

1000

CONV1−OUT

a

Limited to ±199.99 %

This FB is used to multiply analog signals with a specified factor. The calculation is done according
to the following formula:

CONV1−OUT

+ CONV1−IN @ C0940

C0941

Example:

l

You want to multiply an analog signal with 1.12.

l

For this, enter C0940 = 112 and C0941 = 100.

CONV2

CONV2

CONV2−OUT

CONV2−IN

C0948

C0947

C0945
C0946

Fig. 2−58

Conversion (CONV2)

Signal

Source

Note

Name

Type

DIS

DIS format

CFG

List

Lenze

CONV2−IN

a

C0948

dec [%]

C0947

1

1000

CONV2−OUT

a

Limited to ±199.99 %

This FB is used to multiply analog signals with a specified factor. The calculation is done according
to the following formula:

CONV2−OUT

+ CONV2−IN @ C0945

C0946