Configuration – Lenze EVF9383 User Manual

Page 155

Advertising
background image

Configuration

2−147

l

EDSVF9383V−EXT EN 2.0

2.4.50.1

Control characteristic

In the default setting, the PID algorithm is active.

l

The D component is deactivated with

– C0224 = 0 for PCTRL1,

– C1334 = 0 for PCTRL2.

l

The I−component is switched on or off online via the PCTRLx−I−OFF input. For this, the input is
assigned a digital signal source (e.g. one of the freely assignable digital input terminals). If the
I−component is to be switched off permanently, the input is assigned the signal source
FIXED1.

– PCTRLx−I−OFF = HIGH switches off the I−component.

– PCTRLx−I−OFF = LOW switches on the I−component.

l

The adjustment time T

n

is parameterized via

– C0223 for PCTRL1,

– C1333 for PCTRL2.

Gain V

p

for PCTRL1

You can adapt the gain V

p

in different ways. The function for the provision of the gain V

p

is selected

under C0329:

l

C0329 = 0

– The gain V

p

is entered under C0222.

l

C0329 = 1

– The gain V

p

is entered using the input PCTRL1−ADAPT. The input value is led via a linear

characteristic. The shape of the characteristic is set under C0222 (upper limit) and C0325
(lower limit). The value under C0222 is valid if the input value = +100 % or −100 %. The
value under C0325 is valid if the input value = 0 %.

0

100 %

PCTRL1−ADAPT

V

p

V

p1

V

p2

Input data:
V

p1

= C0222

V

p2

= C0325

Display value:
V

pact

= C0336

Fig. 2−123

The gain V

p

is entered via input PCTRL1−ADAPT

Advertising