Configuration – Lenze EVF9383 User Manual

Page 124

Advertising
background image

Configuration

2−116

l

EDSVF9383V−EXT EN 2.0

Range of functions

l

Mains failure detection

l

Mains failure control

l

Restart protection

l

Reset of the mains failure control

l

Dynamic adaptation of the control parameters

l

Fast mains recovery (KU)

l

Application examples

2.4.41.1

Mains failure detection

The type of the mains−failure detection to be used depends on the drive system used.

A failure of the voltage supply of the power stage is detected:

l

by the level of the DC−bus voltage or

l

by an external system (e.g. supply module or voltage−detection relay).

l

Different systems can be combined.

Mains failure detected by the level of the DC−bus voltage

Use with single drives or multi−axis drives, which do not use external monitoring systems.

l

For this, you can use a comparator (e.g. CMP2). Set the following signal links:

– C0688/1 = 5005 (MCTRL−DCVOLT to CMP2−IN1)

– C0688/2 = 19540 (free code C0472/20 to CMP2−IN2)

– C0971 = 10655 (CMP2−OUT to MFAIL−FAULT)

– Set the comparator function CMP2 with C0685 = 3

Enter the function blocks CMP2 and MFAIL at free positions into the processing table under C0465.

C 0 9 8 9 / 1

M F A I L - F A U L T

M F A I L - R E S E T

C 0 9 7 1

C 0 9 7 2

1
0

C 0 9 8 8 / 1

C 0 9 7 0

C 0 9 8 9 / 2

C T R L

M F A I L - N O U T

M F A I L - N - S E T

C 0 9 8 3

C 0 6 8 6

C 0 6 8 7

C 0 6 8 9 / 1

C M P 2

C M P 2 - O U T

C M P 2 - I N 1

C 0 6 8 9 / 2

C M P 2 - I N 2

C 0 6 8 8 / 1

C 0 6 8 8 / 2

C 0 6 8 5

C 0 4 7 2 / 2 0

M C T R L - D C V O L T

M F A I L

Fig. 2−93

Example of a mains failure detection with internal function blocks (section)