Configuration

Use of funktion blocks

2−38

l

EDSVF9383V−EXT EN 2.0

Removing connections

l

Since a source may have several targets, there may be additional signal connections, which
may under certain conditions not be wanted.

l

Example:

– In the default setting of the basic configuration C0005 = 1000 (speed control) ASW1−IN1 and

AIN2−OUT are connected.

– The above−taken steps do not automatically deactivate this connection! If the connection is

not desired, it must be removed.

+ −

*

/

x/(1−y)

C0600

x
y

ARIT2

ARIT2−OUT

C0602/1

"200%

C0602/2

ARIT2−IN1

ARIT2−IN2

C0601/1

C0601/2

62

AOUT1

C434/1

+

+

AOUT1−IN

AOUT1−GAIN

AOUT1−OFFSET

C0434/3

C0434/2

C0431

C0433

C0432

3
4

AIN2

+

+

AIN2−OUT

AIN2−GAIN

AIN2−OFFSET

C0409/1

C0409/2

C0407

C0408

C0108/1

C0109/1

C0027/2

C0026/2

ASW1−IN1

C0812/1

1

0

C0812/2

ASW1−SET

ASW1−IN2

ASW1

ASW1−OUT

C0813

C0810/1
C0810/2

C0811

FIXED0

FIXED0%

NSET−NADD

Fig. 2−18

Removing connections in a configuration

6. Remove the connection between ASW1−IN1 and AIN2−OUT:

– Use

z or y to select C0810/1

– Press PRG to go to the parameter level.

– Use

z or y to select the constant FIXED0% (selection number 1000).

– Confirm with SH + PRG.

– Press PRG to go back to the code level.

The connection has now been removed.

7. Save the new configuration, if necessary:

– Use C0003 and save the new signal configuration in a parameter set to ensure that the

changes will not get lost after mains switching.