Configuration
Use of funktion blocks
2−38
l
EDSVF9383V−EXT EN 2.0
Removing connections
l
Since a source may have several targets, there may be additional signal connections, which
may under certain conditions not be wanted.
l
Example:
– In the default setting of the basic configuration C0005 = 1000 (speed control) ASW1−IN1 and
AIN2−OUT are connected.
– The above−taken steps do not automatically deactivate this connection! If the connection is
not desired, it must be removed.
+ −
*
/
x/(1−y)
C0600
x
y
ARIT2
ARIT2−OUT
C0602/1
"200%
C0602/2
ARIT2−IN1
ARIT2−IN2
C0601/1
C0601/2
62
AOUT1
C434/1
+
+
AOUT1−IN
AOUT1−GAIN
AOUT1−OFFSET
C0434/3
C0434/2
C0431
C0433
C0432
3
4
AIN2
+
+
AIN2−OUT
AIN2−GAIN
AIN2−OFFSET
C0409/1
C0409/2
C0407
C0408
C0108/1
C0109/1
C0027/2
C0026/2
ASW1−IN1
C0812/1
1
0
C0812/2
ASW1−SET
ASW1−IN2
ASW1
ASW1−OUT
C0813
C0810/1
C0810/2
C0811
FIXED0
FIXED0%
NSET−NADD
Fig. 2−18
Removing connections in a configuration
6. Remove the connection between ASW1−IN1 and AIN2−OUT:
– Use
z or y to select C0810/1
– Press PRG to go to the parameter level.
– Use
z or y to select the constant FIXED0% (selection number 1000).
– Confirm with SH + PRG.
– Press PRG to go back to the code level.
The connection has now been removed.
7. Save the new configuration, if necessary:
– Use C0003 and save the new signal configuration in a parameter set to ensure that the
changes will not get lost after mains switching.