Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

123

Programming and Parameters

Chapter 3

Monitor File

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

MONIT

OR

Speed Met

ers

44

[Speed Ref A]
Displays the first speed reference of the drive in rpm. This parameter can be
sourced from many signals and is the factory default selection for Par 70
[Anlg In1 Sel]. See block diagram Speed Reference Selection on page

347

for

possible source signals.
Note: The maximum value of this parameter was changed from –/+ Par 45
for firmware version 3.001.

Default:

Min/Max:
Units:

Read Only

–/+ 1.3 x Par 45 [Max Ref Speed]

(1)

rpm

16-bit
Int

45

(1)

The value of [Max Ref Speed] cannot exceed 6000 rpm.

47

[Speed Ref A Pct]
Displays the first speed reference of the drive as a percentage of Par 45 [Max
Ref Speed]. This parameter can be sourced from many signals. See block
diagram Speed Reference Selection on page

347

for possible source signals.

Notes: This parameter can be assigned to an analog input. The min. and max.
values of this parameter were changed from –/+100.0 for firmware version
3.001.

Default:

Min/Max:
Units:

Read Only

–/+130.0
%

Real

45

48

[Speed Ref B]
Displays the second speed reference of the drive in rpm. This parameter can
be sourced from many signals. See block diagram Speed Reference Selection
on page

347

for possible source signals.

Note: The maximum value of this parameter was changed from –/+ Par 45
for firmware version 3.001.

Default:

Min/Max:
Units:

Read Only

–/+ 1.3 x Par 45 [Max Ref Speed]

(1)

rpm

16-bit
Int

45

(1)

The value of [Max Ref Speed] cannot exceed 6000 rpm.

49

[Speed Ref B Pct]
Displays the second speed reference of the drive as a percentage of Par 45
[Max Ref Speed]. This parameter can be sourced from many signals. See block
diagram Speed Reference Selection on page

347

for possible source signals.

Note: The min. and max. values of this parameter were changed from –/
+100.0 for firmware version 3.001.

Default:

Min/Max:
Units:

Read Only

–/+130.0
%

Real

45

110

[Ramp In]
Total reference value input to the ramp in rpm.
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+32766 for firmware
version 3.001

Default:

Min/Max:
Units:

Read Only

–/+8192
rpm

16-bit
Int

111

[Ramp In Pct]
Total reference value input to the ramp as a percentage of Par 45 [Max Ref
Speed].
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+100.0 for firmware
version 3.001.

Default:

Min/Max:
Units:

Read Only

–/+200.0
%

Real

45

113

[Ramp Out]
Output of the ramp in rpm.
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+32766 for firmware
version 3.001

Default:

Min/Max:
Units:

Read Only

–/+8192
rpm

16-bit
Int

114

[Ramp Out Pct]
Output of the ramp as a percentage of Par 45 [Max Ref Speed].
Note: The min. and max. values of this parameter were changed from –/
+100.0 for firmware version 3.001.

Default:

Min/Max:
Units:

Read Only

–/+200.0
%

Real

45

117

[Speed Reg In Pct]
Total reference value input to the Speed Regulator as a percentage of Par 45
[Max Ref Speed].
Notes: This parameter can be assigned to an analog output. The min. and
max. values of this parameter were changed from –/+100.0 for firmware
version 3.001.

Default:

Min/Max:
Units:

Read Only

–/+200.0
%

Real