Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 149

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

149

Programming and Parameters

Chapter 3

SPEE

D C

O

MMAND

Speed Regul

at

or

126

[Spd Zero P Gain]
The proportional gain of the speed regulator that is only active when the
value of the speed reference and actual speed = 0. This parameter is only
active when Par 125 [Spd Zero P En] = 1 “Enabled”. Used in the Zero Speed
function.
Note: See Speed Zero Function on page

322

for more information.

Default:

Min/Max:
Units:

3.00

0.00 / 100.00
%

Real

238

[SpdOut FiltGain]
First order lead/lag filter gain on the speed regulator output signal.
Note: This parameter was added for firmware version 3.001.

Default:

Min/Max:

1.000

0.000 / 2.000

Real

239

239

[SpdOut FiltBW]
First order lead/lag filter bandwidth on the speed regulator output signal.
Note: This parameter was added for firmware version 3.001.

Default:

Min/Max:
Units:

0

0 / 2000
ms

16-bit
Int

238

242

[Speed Reg En]
Enables/Disables the speed regulator output to the torque/current regulator.
“Enabled” = The speed regulator output is connected to the input of the

torque/current regulator.

“Disabled” = The speed regulator output is not connected to the input of

the torque/current regulator. Par 39 [Torque Ref] is connected to the input
of the current regulator.

Note: This parameter is only available for use with firmware version 2.005
and lower.

Default:

Options:

1 =

0 =
1 =

“Enabled”

“Disabled”
“Enabled”

16-bit
Int

39,
41,
236

348

[Lock Speed Integ]
Enables or disables the integral (I) function of the speed regulator.
“Not active” = The integral component of the speed regulator is enabled.
“Active” = The integral component of the speed regulator is disabled.

Default:

Options:

1 =

0 =
1 =

“Not active”

“Active”
“Not active”

16-bit
Int

388

[Flying Start En]
Enables/Disables the ability of the drive to connect to a spinning motor at
actual rpm when a start command is issued.
“On” = When the drive is turned on, the speed of the motor is measured

and the ramp output is set accordingly. The drive then runs at the set
reference value.

“Off” = When the drive is turned on, the ramp starts from zero.

Main uses:

To connect to a motor that is already spinning due to its load (for example,

in the case of a pump, the flowing medium).

Re–connection to a spinning motor after a fault or alarm.
Note: If the Flying Start function is disabled (off), be sure that the motor is
not spinning when the drive is turned on, or harsh motor deceleration in
current limit may occur.

Default:

Options:

0 =

0 =
1 =

“Off”

“Off”
“On”

16-bit
Int

433

[Total Inertia]
Time, in seconds, for a motor coupled to a load to accelerate from zero to base
speed with rated motor torque applied. This value can be calculated by
Autotune or entered directly.
Note: This parameter was added for firmware version 6.001.

Default:

Min/Max:
Units:

1.0

0.001 / 300.0
s

Real

434

[Spd Reg BW]
Sets the bandwidth of the speed regulator in rad/sec. Bandwidth is also
referred to as the crossover frequency. Small signal time response is
approximately 1/BW and is the time to reach 63% of setpoint. A change to
this parameter will cause an automatic update of Pars 87 [Spd Reg Kp] and 88
[Spd Reg Ki]. To disable the automatic gain calculation, set this parameter to
a value of zero. Note: This parameter was added for firmware version 6.001.

Default:

Min/Max:
Units:

10.0

0.0 / 100.0
rad / sec

Real

87,
88

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

ATTENTION: Failure to correctly set speed and voltage parameters or provide overspeed protection when operating as a
torque/current regulator could result in high motor speeds, equipment damage, and/or personal injury.

A

A

A

A

Advertising
This manual is related to the following products: