Rockwell Automation 23P PowerFlex Digital DC Drive User Manual
Page 72

72
Rockwell Automation Publication 20P-UM001K-EN-P - July 2014
Chapter 1
Installation and Wiring
Table 23 - Frame D, Series B Heatsink Cooling Fan Terminal Designations
Table 24 - Frame D Heatsink Cooling Fan Signal Wire Sizes and Terminal Specifications
Figure 51 - Frame D Heatsink Cooling Fan Terminal Block Location
Terminal Block
Terminal
Description
AC Voltage
Max Current
U3
Three-phase AC input
power connections
400…460V AC
(50/60 Hz)
1.5 A
V3
W3
PE
Safety ground
–
–
31
Normally closed contact
250V AC
1 A
32
Terminals
Wire Size and Type
(1)
(1) See Cable and Wiring Recommendations on page
for more information.
Tightening Torque
N•m (lb•in)
Flexible (mm
2
)
Multi-core (mm
2
)
AWG
U3, V3, W3, 31, 32, PE
0.14…1.5
0.14…2.5
28…12
0.5…0.6 (4.4…5.3)
U3 V3
W3 PE 31 32
U3 V3
W3 PE 31 32
Top View
of Drive
Series B terminal
block shown