Table 82, Table 83 – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 260

Advertising
background image

260

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Appendix A

Supplemental Drive Information

Alternate Dynamic Brake
Resistor Kits and DC Output
Contactors

The following alternate dynamic brake resistor kits and/or DC output contactors
may be used with the corresponding PowerFlex DC drives but must be sourced
separately from the drive.

Table 82 - 575V AC Input Drives

Table 83 - 690V AC Input Drives

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC
Line
Amps

Hp

Armature
Voltage
(Volts)

DB Resistor
Size (ohms)

DC Loop Contactor Cat. No.

(1)

DC
Contactor
Crimp Lugs
Cat. No.

(2)

Drive w/No Dynamic Brake

Drive w Dynamic Brake

B

067

67.5

55.1

50

600

5.93

ABB_EHDB220C2P-1L2S

ABB_EHDB220C-1L22SS

(3)

101

101

83

75

600

3.95

ABB_EHDB220C2P-1L2S

ABB_EHDB220C-1L22SS

135

135

110

100

600

2.96

ABB_EHDB220C2P-1L2S

ABB_EHDB220C-1L22SS

270

270

221

200

600

1.48

ABB_EHDB360C2P-1L2S

ABB_EHDB360C-1L22SS

405

405

331

300

600

0.988

ABB_EHDB520C2P-1L2S

ABB_EHDB520C-1L22SS

C

540

540

441

400

600

0.741

ABB_EHDB650C2P-1L2S

ABB_EHDB650C-1L22SS

675

675

551

500

600

0.593

ABB_EHDB800C2P-1L2S

ABB_EHDB800C-1L22SS

D

810

810

662

600

600

0.494

ABB_EHDB960C2P-1L2S

ABB_EHDB960C-1L22SS

1K0

1080

882

800

600

0.370

SIEMENS-MFG_14-193-101-58-2 (Qty 2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

1K2

1215

993

900

600

0.329

SIEMENS-MFG_14-193-101-58-2 (Qty 2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

1K3

1350

1103

1000

600

0.296

CUTLER-HAMMER_6702ED636-2 (Qty 2)

CUTLER-HAMMER_6702ED636-2 (Qty 1)

1K6

1688

1379

1250

600

0.237

CUTLER-HAMMER_6702ED636-2 (Qty 2)

CUTLER-HAMMER_6702ED636-2 (Qty 1)

(1) Coil voltage = 115V AC, 50/60Hz.
(2) See DC Contactor Crimp Lug Kit Specifications on page

264

for more information.

(3) Wire and Lug size dependant on enclosure dimensions and local codes.

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC
Line
Amps

Hp

Armature
Voltage
(Volts)

DB Resistor
Size (ohms)

DC Loop Contactor Cat. No.

(1)

DC
Contactor
Crimp Lugs
Cat. No.

(2)

Drive w/No Dynamic Brake

Drive w Dynamic Brake

C

452

452

369

400

700

1.03

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

(3)

565

565

462

500

700

0.826

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

D

678

678

554

600

700

0.688

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

791

791

646

700

700

0.590

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

904

904

739

800

700

0.516

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

1K0

1017

831

900

700

0.459

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

1K1

1130

923

1000

700

0.413

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

1K2

1243

1016

1100

700

0.375

SIEMENS-MFG_14-193-101-58-2 (Qty
2)

SIEMENS-MFG_14-193-101-58-2 (Qty 1)

1K4

1413

1154

1250

700

0.330

CUTLER-HAMMER_6702ED636-2 (Qty 2) CUTLER-HAMMER_6702ED636-2 (Qty 1)

1K5

1582

1292

1400

700

0.295

CUTLER-HAMMER_6702ED636-2 (Qty 2) CUTLER-HAMMER_6702ED636-2 (Qty 1)

(1) Coil voltage = 115V AC, 50/60Hz.
(2) See DC Contactor Crimp Lug Kit Specifications on page

259

for more information.

(3) Wire and Lug size dependant on enclosure dimensions and local codes.

Advertising
This manual is related to the following products: