Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 199

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

199

Programming and Parameters

Chapter 3

INPUT

/

OUTPUT

D

igi

tal

O

u

tpu

ts

145
146
147
148
149
150
151
152

[Digital Out1 Sel]
[Digital Out2 Sel]
[Digital Out3 Sel]
[Digital Out4 Sel]
[Digital Out5 Sel]*
[Digital Out6 Sel]*
[Digital Out7 Sel]*
[Digital Out8 Sel]*
Selects the source of the value that drives the digital output. See Option
Definitions for [Digital Outx Sel], [Relay Out 1 Sel] and [Relay Out 2 Sel]
on
page

200

.

*These parameters are used to configure the digital outputs on the I/O
Expansion circuit board.
Notes: Option 16 “Encoder Err” was changed for firmware version v5.002.
Option 30 “Brake Slip” was added for firmware version 6.001.
Options:

Default:
Default:
Default:
Default:
Default:
Default:
Default:
Default:

5 =
9 =
2 =
4 =
26 =
0 =
0 =
0 =

“Ready”
“Fault”
“Spd Thresh”
“CurrentLimit”
“Alarm”
“Not Used”
“Not Used”
“Not Used”

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

0 =

“Not Used” (Off)

8 =

“Spd Limited”

16 = “Spd Fdbk Err”

24 = “Reserved”

1 =

“Spd Zero Thr”

9 =

“Fault”

17 = “Diam Calc”

25 = “Reserved”

2 =

“Spd Thresh”

10 = “Power Loss”

18 = “Input1 Cmp”

26 = “Alarm”

3 =

“At Speed”

11 =

“UserDefinedA”

19 = “Diam Reached”

27 = “Running”

4 =

“CurrentLimit”

12 =

“UserDefinedB”

20 = “Speed Match”

28 = “Jogging”

5 =

“Ready”

13 = “Stop Control”

21 = “Accelerating”

29 = “Active”

6 =

“Ramp Pos”

14 =

“Field Loss”

22 = “Decelerating”

30 = Brake Slip

7 =

“Ramp Neg”

15 =

“Spd Fbk Loss”

23 = “Brake Cmd”