Table 49 - 575V AC Input Drives

Frame A and B Armature DC Output Fuses

Armature DC output fuses are externally mounted for frame A and B drives and
must be sourced separately. These fuses are required on four quadrant drives only,
but highly recommended on two quadrant drives. See Fuse Code FS2 in

Figure 68

on page

236

.

Table 50 - 230V AC Input Drives

Frame

Drive Current
Rating Code

DC Amps

AC Line
Amps

Bussmann

Mersen

North American FWP Type North American A70QS Type

B

067

67.5

55.1

FWP-100A

A70QS100-4

101

101.3

82.7

FWP-175A

A70QS175-4K

135

135

110.3

FWP-225A

A70QS225-4

270

270

220.6

FWP-450A

A70QS450-4

405

405

330.9

FWP-600A

A70QS600-4K

Fr

am

e

Drive
Current
Rating
Code

DC
Amps

AC Line
Amps

Bussmann

Mersen

Ferrule FWP Type

North American
FWP Type

Ferrule A70QS
Type

North American
A70P / A70QS
Type

A 7P0

7

5.7

FWP-15A14F

FWP-15B

A70QS16-14F

A70P15-4

9P0

9

7.4

FWP-20A14F

FWP-20B

A70QS20-14F

A70P20-4

012

12

9.8

FWP-25A14F

FWP-25B

A70QS25-14F

A70P25-4

020

20

16

FWP-40A14F

FWP-40B

A70QS40-14F

A70QS40-4

029

29

24

FWP-63A22F

FWP-60B

A70QS63-22F

A70QS60-4

038

38

31

FWP-80A22F

FWP-80B

A70QS80-22F

A70QS80-4

055

55

45

FWP-125A

A70QS125-4K

073

73

60

FWP-150A

A70QS150-4K

093

93

76

FWP-200A

A70QS200-4K

110

110

90

FWP-225A

A70QS250-4

B 146

146

119

FWP-300A

A70QS300-4

180

180

147

FWP-350A

A70QS350-4

218

218

178

FWP-450A

A70QS450-4

265

265

217

FWP-600A

A70QS600-4K

360

360

294

FWP-700A

A70QS700-4

434

434

355

FWP-900A

A70P900-4

Advertising
This manual is related to the following products: