Verify the control voltages, Load the default settings, Configure the most commonly used parameters – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 95

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

95

Drive Start Up

Chapter 2

Verify the Control Voltages

Verify that the following voltages are present at I/O terminal block 1 and
2. See I/O Signal and Control Wiring on page

81

:

Load the Default Settings

It is recommended that you reset the drive to the default settings. By resetting the
drive to the default settings, any previous parameter modifications you have made
will be overwritten.

1.

On the HIM, from the “Main” menu scroll to the “Memory Storage”
menu.

2.

Press Enter.

3.

Scroll to “Reset To Defaults” and press Enter.\
A message displays to verify that you want to reset the drive to the
factory settings.

4.

Press Enter.
Note: A “Params Defaulted” (F48) entry will be made in the drive’s Fault
Queue to indicate the change.

Configure the Most Commonly Used Parameters

If your application only requires basic drive parameter set up, you can use the
S.M.A.R.T. list screen available on the HIM to program the drive. See Using the
S.M.A.R.T. List Screen on
page

267

for more information.

Terminal Number…

Voltage

to Terminal Number…

7

+10V

9

8

-10V

9

19

+24 - 30V

18

IMPORTANT

To access all parameters in this procedure you must set the Parameter View
option to “Advanced”.