Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 1

Installation and Wiring

Table 32 - Drives with 690V Input - DIP Switch S15 Configuration

I/O Wiring

Observe the following points when installing I/O wiring:

Use copper wire only.

Wire with an insulation rating of 600V or greater is recommended.

Frame

Drive Current

Rating Code

S15-1

S15-2

S15-3

S15-4

S15-5

S15-6

S15-7

S15-8

C

452

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

565

ON

OFF

OFF

OFF

OFF

OFF

ON

ON

D

678

OFF

ON

OFF

OFF

OFF

OFF

ON

ON

791

ON

ON

OFF

OFF

OFF

OFF

ON

ON

904

ON

OFF

ON

OFF

OFF

OFF

ON

ON

1K0

OFF

ON

ON

OFF

OFF

OFF

ON

ON

1K1

ON

ON

ON

OFF

OFF

OFF

ON

ON

1K2

OFF

OFF

OFF

ON

OFF

OFF

ON

ON

1K4

OFF

ON

OFF

ON

OFF

OFF

ON

ON

1K5

ON

ON

OFF

ON

OFF

OFF

ON

ON

IMPORTANT

I/O terminals labeled “(–)” or “Common” are not referenced to earth ground
and are designed to greatly reduce common mode interference. Grounding
these terminals can cause signal noise.

ATTENTION: Configuring an analog input for current operation and driving it from
a voltage source could cause component damage. Verify proper switch
configuration prior to applying input signals. See DIP Switch and Jumper Settings
on page

75

.

ATTENTION: Hazard of personal injury or equipment damage exists when bipolar
input sources are used. Noise and drift in sensitive input circuits can cause
unpredictable changes in motor speed and direction. Use speed command
parameters to help reduce input source sensitivity.