Frame c and d armature fuse signal terminals – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 73

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

73

Installation and Wiring

Chapter 1

Frame C and D Armature Fuse Signal Terminals

Terminals 81 and 82 on frame C and D drives are connected to the indicating
switch mounted on each of the internal armature circuit protection fuses. These
terminals can be connected to an external device to provide indication that the
fuses have opened. Alternatively, terminals 81 and 82 can be wired to drive digital
input terminals configured for 64 “Invert Flt” (via Pars 133…144).

Table 25 - Armature Fuse Signal Terminal Designations

Table 26 - Armature Fuse Signal Wire Size and Terminal Specifications

Figure 52 - 230V/460V AC Input Frame C Internal Armature Fuse Signal Terminal Block Location

Terminal

Description

Maximum Voltage

Maximum Current

81

Internal armature fuse intervention signal.

250V AC

1 A

82

Terminals

Wire Size and Type

(1)

(1) See Cable and Wiring Recommendations on page

43

for more information.

Tightening Torque
N
m (lbin)

Flexible
(mm

2

)

Multi-core
(mm

2

)

AWG

81,

82

0.14…1.5 0.14…2.5 26…16

0.4

(3.5)

81

82

Advertising