Armature converter connections – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 50

Advertising
background image

50

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 1

Installation and Wiring

Armature Converter Connections

Table 11 - Armature and Safety Ground (PE) Terminal Specifications

Figure 23 - Frame A Armature Converter Terminal Locations

Terminals

Description

U, V, W

Three phase AC input to the armature converter

C, D

DC output to the motor armature

PE

Safety ground

Fram

e

Drive Current Rating Code

(1)

Terminals

Wire Size and Type

Terminal Bolt
Size (mm)

Tightening
Torque
N
m (lbin)

230V

460V

575

690

A

7P0…055

4P1…052

U, V, W, C, D, PE

See Cable and Wiring

Recommendations on

page

43

5

6 (53)

073…110

073…129

Terminal Block

12 (106)

B

All

All

All

U, V, W, C, D

10

25 (221)

PE

8

15 (132.75)

C

All

All

All

All

U, V, W, C, D

10

25 (221)

PE

8

15 (132.75)

D

All

All

All

All

U, V, W, C, D, PE

12

45 (398.2)

(1) See Standard Drive Catalog Number Explanation on page

15

, positions 8, 9 and 10 for corresponding drive HP rating, armature amp rating and

field amp rating.

IMPORTANT

Certain frame D drives require the use of a terminal adapter kit(s) for terminals
U, V, W, C and D. See Terminal Adapter Kits for Frame D Drives on page

264

for

details.

U

C

V

D

W

PE

Front View

ATTENTION: Do not operate the drive with the power terminal cover removed.
Operating the drive with the power terminal cover removed may result in a
hazardous condition that could cause personal injury and/or equipment
damage.

Note: Front view of drive shown with bottom protective and power terminal covers removed. See Remove the
Drive Covers on
page

27

for information on removing the drive covers.

Advertising