Speed command file – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 145

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

145

Programming and Parameters

Chapter 3

Speed Command File

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

SPEE

D C

O

MMAND

Limits

1

[Minimum Speed]
Defines the minimum speed of the drive. This value applies to both directions
of motor rotation for four quadrant drives. A speed below the value set in
[Minimum Speed] is not possible, regardless of the set speed reference value.
If the value of [Minimum Speed] is changed, Pars 5 [Min Speed Fwd] and 6
[Min Speed Rev] are set to the same value. If either Par 5 [Min Speed Fwd] or
Par 6 [Min Speed Rev] is changed later, the last change is valid.

Default:

Min/Max:
Units:

0

0 / Par 45 [Max Ref Speed]
rpm

32-bit
Int

5,
6

2

[Maximum Speed]
Defines the maximum speed of the drive. This value applies to both
directions of motor rotation for four quadrant drives. The value of this
parameter is input to the speed regulator and therefore takes into account
the reference value that comes from the ramp as well as the direction of
rotation. If the value of [Maximum Speed] is changed, Pars 3 [Max Speed
Fwd] and 4 [Max Speed Rev] are set to the same value. If either Par 3 [Max
Speed Fwd] or Par 4 [Max Speed Rev] is changed later, the last change is
valid.

Default:

Min/Max:
Units:

1750

0 / Par 45 [Max Ref Speed]
rpm

32-bit
Int

3,
4

3

[Max Speed Fwd]
Defines the maximum speed for forward (clockwise) rotation of the motor.
The value of [Max Speed Fwd] affects the input of the speed regulator and
therefore takes into account both the reference values that come from the
ramp as well as the direction of motor rotation.

Default:

Min/Max:
Units:

1750

0 / Par 45 [Max Ref Speed]
rpm

32-bit
Int

2

4

[Max Speed Rev]
Defines the maximum speed for reverse (counterclockwise) rotation of the
motor for four quadrant drives only. The value of [Max Speed Rev] affects the
input of the speed regulator and therefore takes into account both the
reference values that come from the ramp as well as the direction of rotation.

Default:

Min/Max:
Units:

1750

0 / Par 45 [Max Ref Speed]
rpm

32-bit
Int

2

5

[Min Speed Fwd]
Defines the minimum speed for forward (clockwise) rotation of the motor.
Speed reference values below the value in this parameter are clamped until
the reference exceeds this limit.

Default:

Min/Max:
Units:

0

0 / Par 45 [Max Ref Speed]
rpm

32-bit
Int

1

6

[Min Speed Rev]
Defines the minimum speed for reverse (counterclockwise) rotation of the
motor for four quadrant drives only. Speed reference values below the value
in this parameter are clamped until the reference exceeds this limit.

Default:

Min/Max:
Units:

0

0 / Par 45 [Max Ref Speed]
rpm

32-bit
Int

1

Discr

et

e Speeds

154
155
156
157
158
159
160

[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]
Provides an internal fixed speed command value. In bipolar mode, direction
is commanded by the sign of the reference.
Notes: [Preset Speed 1] cannot be directly selected by the Speed Sel digital
inputs. However, Par 154 [Preset Speed 1] can be directed to Par 42 [Trim
Ramp] via the Scale Block parameters. See Reference Control on page

307

for

more information.

Default:
Default:
Default:
Default:
Default:
Default:
Default:

Min/Max:
Units:

150
300
600
900
1200
1500
1750

-/+6000
rpm

16-bit
Int

266

[Jog Speed]
Reference value for jog mode.
Notes: This parameter can be assigned to an analog input. See Reference
Control o
n page

307

for more information.

Default:

Min/Max:
Units:

100

-/+6000
rpm

16-bit
Int

Advertising