Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

329

Application Notes

Appendix C

Sum Mode

Sum mode is selected when Par 241 [Spd Torq Mode Sel] is set to 5 “Sum”. In this
mode, the reference is derived from the sum of the speed regulator output (Par
236 [Spd Reg Out Pct]) and the torque reference (Par 39 [Torque Ref ]). This
mode can be used for applications that have precise speed changes with critical
time constraints.

Torque Mode Selection Status Bits

Bits 7 “Forced Spd”, 8 “Speed Mode”, and 9 “Torque Mode” of parameter 382
[Drive Status 2] display the current status of the speed/torque mode for the drive.

(1) 3 “SLAT Min”

(2) 4 “SLAT Max”

Note: When Par 241 [Spd Trq Mode Sel] is changed to 1 “Speed Reg”, the speed
regulator integrator is preloaded with the value of Par 14 [Selected Torque Ref ].
When Par 241 [Spd Trq Mode] is changed to 5 “Sum”, the speed regulator is
preloaded with the value of Par 14 [Selected Torq Ref ] - Par 39 [Torque Ref ]
(Par 14 - Par 39).

Par 241
[Spd Trq Mode Sel]

Par 382 [Drive Status 2]
Bit 7 “Forced Spd

Bit 8 “Speed Mode”

Bit 9 “Torque Mode”

(1)

(1) b9 = not(b7 + b8), if b7=1 & b8=0, then b9=0.

0 “Zero Trq Ref”

0

0

1

1 “Speed Reg”

0

1

0

2 “Torque Reg”

0

0

1

3 “SLAT Min”

(1)

4 “SLAT Max”

(2)

5 “Sum”

0

1

1

Bit 7 “Forced Spd

0

Not in Forced Speed Mode (FSM)

0 -> 1

Speed error < 0 (i.e., Feedback > Reference), preload the speed regulator
integrator with the value of Par 14 [Selected Torque Ref]

1

Forced Speed Mode (FSM), speed error < 0

1 -> 0

Error (i.e., Reference - Feedback) > Par 15 [SLAT Err Stpt] for more than the value of
Par 16 [SLAT Dwell Time]

Bit 8 “Speed Mode”

0

Par 236 [Spd Reg Pct Out] > Par 39 [Torque Ref]

1

Par 236 [Spd Reg Pct Out] < Par 39 [Torque Ref]

Bit 7 “Forced Spd

0

Not in Forced Speed Mode (FSM)

0 -> 1

Speed error > 0 (i.e., Feedback < Reference), preload the speed regulator
integrator with the value of Par 14 [Selected Torque Ref]

1

Forced Speed Mode (FSM), speed error > 0

1 -> 0

Error (i.e., Reference - Feedback) < -Par 15 [SLAT Err Stpt] for more than the value
of Par 16 [SLAT Dwell Time]

Bit 8 “Speed Mode”

0

Par 236 [Spd Reg Pct Out] < Par 39 [Torque Ref]

1

Par 236 [Spd Reg Pct Out] > Par 39 [Torque Ref]

b7 b8

+

(

)

b7 b8

+

(

)