Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 174

Advertising
background image

174

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 3

Programming and Parameters

UTILIT

Y

D

iagnos

tics

346

[Torque Positive]
Indicates whether the drive is operating with a positive torque reference.
1 “Active” = The drive is operating with a positive torque reference. The motor

is accelerating in the forward direction or decelerating in the negative direction
and Par 20 [Ramp Delay] has timed out.

0 “Not Active” = The drive is not operating with a positive torque reference.
Note: This parameter can be assigned to a digital output.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

20

347

[Torque Negative]
Indicates whether the drive is operating with a negative torque reference.
1 “Active” = The drive is operating with negative torque reference. The motor is

accelerating in the reverse direction or decelerating in the forward direction
and Par 20 [Ramp Delay] has timed out.

0 “Not Active” = The drive is not operating with negative torque reference.
Note: This parameter can be assigned to a digital output and is used for four
quadrant drives only.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

20

349

[CurrLimit Active]
Indicates whether or not the drive is working within the set current limits.
1 “Active” = The drive is currently in a current limited state.
0 “Not Active” =The drive is not in a current limited state.
Note: This parameter is assigned to digital output 4 (Par 148 [Digital Out4 Sel]) by
default.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

372

[Spd Limit Active]
Indicates whether the current speed reference value is limited by the defined
minimum and maximum limit values.
1 “Active” = The reference value is currently limited because the value entered

is out of range of the limit values defined.

0 “Not Active” = The reference value is within the defined limit values.
Note: This parameter can be assigned to a digital output.

Default:

Min/Max:

Read Only

0 / 1

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

Advertising