Mount the Drive

Operating Conditions and Temperatures

PowerFlex DC drives are designed to operate at 0…50 °C (32…122 °F)
surrounding air temperature without derating. The drive must be mounted in a
clean, dry location. Contaminants such as oils, corrosive vapors, and abrasive
debris must be kept out of the enclosure. NEMA / UL Type Open, IP20
enclosures are intended for indoor use primarily to provide a degree of protection
against contact with enclosed equipment. These enclosures offer no protection
against airborne contaminants.

Minimum Mounting Clearances

Minimum clearance requirements are intended to be from drive to drive. Other
objects can occupy this space; however, reduced airflow can cause protection
circuits to fault the drive. The drive must be mounted in a vertical orientation as
shown in

Figure 1

and must not be mounted at an angle greater than 30° from

vertical. Intake air temperature must not exceed the product specification.

Figure 1 - Drive Enclosure Minimum Mounting Clearances

Maximum Surrounding Air Temperature Specifications

0…50 °C (32…122 °F), typical

De-rate 1.25% for every 1 °C (°F) over 50 °C (122 °F), to 55 °C (131 °F)

Additional cooling is required for temperatures above 55 °C (131 °F)

10 mm

10 mm

50 mm

(0.4 in.)

(0.4 in.)

(2.0 in.)

10 mm
(0.4 in.)

150 mm (6.0 in.)

150 mm (6.0 in.)

150 mm (6.0 in.)

STS

PORT

MOD

NET A

NET B

STS

PORT

MOD

NET A

NET B

Airflow through the drive
must not be impeded.