126

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 3

Programming and Parameters

MONIT

OR

Cu

rre

n

t M

ete

rs

232

[Inertia Comp Out]
Displays the output of the Inertia Compensation function. The [Inertia Comp
Out] signal (if selected by Par 1016 [SpdFuncSelect]) is summed with Pars 14
[Selected TorqRef] and 40 [Trim Torque]. Inertia compensation provides a
torque feed forward signal during changes in motor speed reference.
Note: This parameter was added for firmware version 4.001.

Default:

Min/Max:
Units:

Read Only

–/+200
%

Real

234

[Fld Current Pct]
Field current (present value) as a percentage of Par 280 [Nom Mtr Fld Amps].
When running a permanent magnet motor, this parameter will display zero.
Note: This parameter can be assigned to an analog output and is the default
value for Par 68 [Anlg Out3 Sel].

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

280

236

[Spd Reg Out Pct]
Output value of the speed regulator, as a percentage of Par 179 [Nom Mtr
Arm Amps], used as the reference for the current regulator.

Default:

Min/Max:
Units:

Read Only

–/+250
%

Real

179

351

[Field Current]
Present value of the field current. When running a permanent magnet motor,
this parameter will display zero.
Note: This parameter can be assigned to an analog output.

Default:

Min/Max:
Units:

Read Only

0.00 / 99.90
A

Real

476

[Field Curve Out]
Displays the output value of the field current used as a reference to the field
current regulator.
Note: This parameter was added for firmware version 4.001.

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

500

[Flux Ref Pct]
Field flux (reference) as a percentage of Par 280 [Nom Mtr Fld Amps]. When
running a permanent magnet motor, this parameter will display zero.
Notes: This parameter can be assigned to an analog output. This name of this
parameter was changed from [Field Ref Pct] for firmware version 3.001.

Default:

Min/Max:
Units:

Read Only

0.00 / 100.00
%

Real

280

928

[Filt TorqCur Pct]
Filtered value of Par 1193 [Torq Current Pct]. The amount of filtering is set by
Par 926 [Torq Cur Filter].

Default:

Min/Max:
Units:

Read Only

–/+250
%

16-bit
Int

926,
1193

Dr

iv

e Da

ta

57

[FaultCode]
A code that shows the last active fault on the drive. If there are no active
faults, this value will be zero (No Fault). The last 10 faults in the drive can be
viewed in Pars 1351…1370. See Fault Descriptions on page

218

for a list of

fault codes and descriptions.

Default:

Min/Max:

Read Only

0 / 65535

16-bit
Int

1351

233

[Output Voltage]
Measured output armature voltage.
Note: This parameter can be assigned to an analog output and is the default
selection for Par 69 [Anlg Out4 Sel].

Default:

Min/Max:
Units:

Read Only

-/+999.00
Vdc

Real

235

[Elapsed Lifetime]
Shows the operating time of the drive. This parameter counts the time for
which the drive is energized (even if the drive is disabled).

Default:

Min/Max:
Units:

Read Only

0.00 / 65535.0
H.m

Real

300

[Drive Type]
Displays of the drive type.
“10” = Non-Regenerative
“11” = Regenerative

Default:

Min/Max:

Read Only

10 / 11

16-bit
Int

331

[Software Version]
Displays the Major and Minor (Major.Minor) firmware version numbers active
in the drive.

Default:

Min/Max:

Read Only

1.00 / 999.00

Real

332

[Drive Checksum]
Provides a checksum value that indicates whether or not a change in drive
programming has occurred.

Default:

Min/Max:

Read Only

0 / 65535

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted