Power circuit protection, Control power circuit protection – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 42

Advertising
background image

42

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 1

Installation and Wiring

Power Circuit Protection

It is recommended that you install frame A and B PowerFlex DC drives with fast
acting fuses to protect the armature converter on the AC input and DC output
(for four quadrant drives only) sides. Internally mounted fuses for armature
converter protection are provided with frame C and D PowerFlex DC drives. See
Drive Power Circuit Protection on page

236

for a list of replacement fuses and

general fuse locations.

Control Power Circuit
Protection

The 115V / 230V AC control circuit power input terminals U2 and V2 are
required to be short circuit protected. This protection can be provided by using
standard time delay fuses or a circuit breaker. The time delay fuses or circuit
breaker must be selected to survive the short circuit available current of the feeder
source for this circuit and the inrush current of the drive’s power supply.

Size the fuses or circuit breaker to primarily protect the wiring from the fuses or
circuit breaker connections to terminals U2 and V2, and not nuisance trip or
blow from the inrush current.

The table below lists the input current characteristics of the control power.

Table 10 - Control Power Protection

Provide a control power input supply from a power source that is stabilized and
buffered from the power system transients. The control power of many drives can
be fed from a single source, as long as proper distribution protection is provided.

Frame

Control Power Supply

Circuit Board ID / Revision

Power

Rated input current

Inrush input current

115V AC

230V AC

115V AC

230V AC

A & D

SW1-31 / H & below

60 W

1 A

0.5 A

20 A

10 A

SW1-31 / I & above

80 W

1 A

0.5 A

6 A

10 A

B

SW2-32 / H & below

110 W

1.2 A

0.7 A

15 A

7.5 A

SW2-32 / I & above

90 W

1.2 A

0.6 A

6 A

10 A

C

SW3-32 / H & below

110 W

1.2 A

0.7 A

15 A

7.5 A

SW3-32 / I & above

90 W

1.2 A

0.6 A

6 A

10 A