[Torque Reduction]
Selection for torque reduction. When the torque reduction function is active
(1 “Active”), the current limit changes accordingly by the percentage defined
in Par 13 [Torq Red CurLim]. When this parameter is set to 0 “Not Active”,
torque reduction is not active.
For example:

Par 7 [Current Limit] (or Pars 8 [Current Lim Pos] and 9 [Current Lim Neg])
= 80%
Par 13 [Torq Red CurLim] = 70%
If Par 342 [Torque Reduction] = 0 “Not Active”, the current limit = 80%
If Par 342 [Torque Reduction] = 1 “Active”, the current limit = 70%

Note: This parameter can be assigned to a digital input.

Default:

Options:

0 =

0 =
1 =

“Not Active”

“Not Active”
“Active”

16-bit
Int

13

353

[Zero Torque]
Sets the reference value for the armature current (Par 41 [Current Reg In]) to
zero so that the drive has no torque.
“Not Active” = Par 41 [Current Reg In] is not set to zero.
“Active” = Par 41 [Current Reg In] is set zero. The drive has no torque.

Default:

Options:

1 =

0 =
1 =

“Not Active”

“Active”
“Not Active”

16-bit
Int

41

750

[TrqTpr Enable]
Enables/Disables the current/speed curve function.
“Disabled” = The limits current /speed curve is disabled
“Enabled” = The limits current /speed curve is enabled
Note: See Current / Speed Curve on page

278

for more information.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

751,
752,
753,
754,
755,
756

751

[TrqTpr Lim0]
The current limit of the current/speed curve that operates constantly up to
the speed set in Par 756 [TrqTpr Spd]. When the current/speed curve function
is enabled (set in Par 750 [TrqTpr Enable]), this parameter will override the
current limits set in Pars 10 [Cur Lim Pos Out] and 11 [Cur Lim Neg Out].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

752

[TrqTpr Lim1]
First reduced current limit of the current/speed curve. The value defined in
this parameter must be less than the value in Par 751 [TrqTpr Lim0] and
greater than the values in Pars 753 [TrqTpr Lim2], 754 [TrqTpr Lim3] and 755
[TrqTpr Lim4].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

753

[TrqTpr Lim2]
Second reduced current limit of the current/speed curve. The value defined in
this parameter must be less than the value in Par 752 [TrqTpr Lim1] and
greater than the values in Pars 754 [TrqTpr Lim3] and 755 [TrqTpr Lim4].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

754

[TrqTpr Lim3]
Third reduced current limit of the current/speed curve. The value defined in
this parameter must be less than the value in Par 753 [TrqTpr Lim2] and
greater than the value in Par 755 [TrqTpr Lim4].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

755

[TrqTpr Lim4]
Last reduced current limit of the current/speed curve. The value defined in
this parameter must be less than the value in Par 754 [TrqTpr Lim3]. The drive
will operate at this current limit up to the value set in parameter 162 [Max
Feedback Spd].

Default:

Min/Max:
Units:

0

0 / 200
%

16-bit
Int

750,
756

756

[TrqTpr Spd]
Threshold speed at which torque reduction begins, as determined by the
current/speed curve.

Default:

Min/Max:
Units:

0

0 / Par 162
rpm

16-bit
Int

750,
756

926

[Torq Cur Filter]
First rate low-pass filter for Par 1193 [Torq Current Pct].
Note: The name of this parameter was changed from [Filt Torq Cur] for
firmware version 3.001.

Default:

Min/Max:
Units:

0.100

0.001 / 0.250
s

Real

1193

Fil

e

Gr

oup

No

.