Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 1

Installation and Wiring

Digital Encoder Terminal Block

Always connect the encoder connection cables directly to the terminals on the
encoder terminal block. The encoder cable must be made up of twisted pairs with
the shield connected to the shield ground on the drive side. Do not connect the
shield to ground on the motor side. In some cases (for example, cable lengths that
exceed 100 meters), it may be necessary to ground the shield of each twisted pair
on the power supply. See the PowerFlex Digital DC Drive Technical Data,
publication

20P-TD001

, for digital encoder specifications.

Figure 59 - Digital Encoder Terminal Block Location

Table 38 - Digital Encoder Terminal Designations

Terminal Block

Label

Signal

Description

A+

Encoder A

Single channel A or dual channel
quadrature A input

A-

Encoder A (NOT)

B+

Encoder B

Single channel B or dual channel
quadrature B input

B-

Encoder B (NOT)

Z+

Encoder Z

Pulse, marker or registration input

(2)

(2) Selectable via switch S20 on the control board. See

Table 27

on page

76

.

Z-

Encoder Z (NOT)

COM

+5/12…15V

(1)

DC Return

Internal power common

+V

+5/12…15V

(1)

DC Power

(1) Selectable via switch S21 on the control board. See

Table 27

on page

76

.

Internal power source
200 mA

Digital Encoder

terminal block

Control board

EMI shield

Wire shield ground

Wire shield ground

A-

B+

B-

Z+

A+

COM

+V

Z-