Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 4

Troubleshooting

Clearing Alarms

Alarms are automatically cleared when the condition that caused the alarm is no
longer present.

Alarm Descriptions

The status of the alarms can be viewed in

1380

[Drive Alarm 1].

Table 42 - Alarm Descriptions and Actions

Alarm

Type

Description

Arm Overvoltage 1

There is a possible overvoltage on the armature circuit or Par

175

[Rated Motor Volt] is set too

low for the application. See the “Arm Overvoltage” fault description on

page 218

for more

information.

Auxiliary Input

1

An auxiliary input interlock is open or a voltage (+15 - 30 V) or reference signal is missing for
the digital input set to 14 “Aux Fault”. See the “Auxiliary Input” fault description on

page 218

for more information.

BipolarCflct

2

Par

1322

[Direction Mode] is set to “Bipolar” or “Reverse Dis” and one or more of the

following digital input functions is configured: “Fwd/Reverse,” “Run Forward,” “Run
Reverse,” “Jog Forward,” “Jog Reverse,” “Rev Dec Limit,” or “Rev End Limit.”

BrakeSlipped

1

The encoder movement has exceeded the level in Par

1110

[Brk Slip Count] after the brake

was set and the brake slip maneuver is controlling the drive (drive is active).
Cycle power to the drive to reset.

2

The encoder movement has exceeded the level in Par

1110

[Brk Slip Count] after the brake

was set and the brake slip maneuver is finished (drive is stopped).
Cycle power to the drive to reset.

CntactrCflct

2

Contactor input functions are in conflict:
When Par

1391

[ContactorControl] is set to “None”, both relay outputs (Pars

1392

[Relay

Out 1 Sel] and

629

[Relay Out 2 Sel] and all digital inputs ([Digital Inx Sel]) cannot be set

to “Contactor” or “ContactorDB”.

With [ContactorControl] set to “AC Cntcr” or “DC Cntcr”, one relay output and one digital

input must be set to “Contactor”. No relay or digital output can be defined as
“ContactorDB”.

With [ContactorControl] set to “AC Cntcr+DB” or “DC Cntcr+DB”, both relay outputs and

one digital input must be set to “Contactor”, “ContactorDB” and “Contactor”, respectively.

Because any relay output can be configured as contactor or DB control and any digital input
as contactor status, care must be taken to correctly wire the terminal blocks to match the
parameter selections.

DigInCflctA

2

Digital input functions are in conflict. Combinations marked with a “ ” will cause an alarm.

Acc2/Dec2 Accel 2 Decel 2 Jog 1/2 Jog Fwd Jog Rev Fwd/Rev

Acc2/Dec2
Accel 2
Decel 2
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev