Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 225

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

225

Troubleshooting

Chapter 4

DigInCflctB

2

One of the following digital input conflicts exists:
A digital Start input has been configured without a Stop input
None of the digital inputs are configured for “Enable”
Other digital input functions are in conflict. Combinations that conflict are marked with a

“ ” and will cause an alarm.

DigInCflctC

2

More than one physical input has been configured to the same input function. Multiple
configurations are not allowed for the following input functions.

Forward/Reverse

Run Reverse

Run Forward

Jog Forward

Jog Reverse

Speed Select 1

Speed Select 2

Speed Select 3

Acc2 / Dec2

Accel 2

Decel 2

Run

FB Cfg Cflct

2

One of the following has occurred:
Par

414

[Fdbk Device Type] does not equal 3 “Armature” and Par

478

[Spd Loss Flt Cfg] is

set to “Alarm” while Par

458

[SpdReg FB Bypass] is set to “Disabled”.

Par 414 [Fdbk Device Type] is set to 4 “Resolver” and Pars

429

[Resolver Pos Sel],

430

[Resolver Spd Sel],

786

[PID Source],

1204

[Line Spd Source], or

1284

[Ref Spd Source] are

selecting a resolver signal.

Par 414 [Fdbk Device Type] is set to 1 “Encoder” and Pars 786, 1021, 1204, or 1284 are

selecting an encoder signal.

FldCfg Cflct

2

The selected operating mode of the field controller is in conflict with another setting in the
drive or a permanent magnet motor is incorrectly configured. This alarm displays under the
following conditions:
Par 469 [Field Mode Sel] = “Field Weaken” or “External” and Par

414

[Fdbk Device Type]

= “Armature”

Par 469 [Field Mode Sel] = “Field Weaken” or “External” and Par

478

[Spd Loss Flt Cfg] =

“Alarm”

Par 469 [Field Mode Sel] = “Field Weaken” or “Base Speed” and Par

497

[Field Reg En] =

“Disabled”

Par 469 [Field Mode Sel] = “Base Speed” and Par

498

[Force Min Field] = “Enabled”

Par 469 [Field Mode Sel] = “Base Speed” and Par

133

144

[Digital Inx Sel] = “Force

Min Fld”

Fld Current Loss

1

The field current is too low. See the “Fld Current Loss” fault description on

page 218

for more

information.

Motor Overload

1

The selected motor overload current level has been exceeded. See the “Motor Overload” fault
description on

page 219

for more information.

Motor Over Temp 1

The motor has exceeded its temperature rating (as signaled by the thermistor connected to
the drive terminals 78 and 79). See the “Motor Over Temp” fault description on

page 219

for

more information.

Ref Cflct

2

1. More than one of the drive's reference inputs (Pars

70

,

75

and

80

[Anlg Inx Sel], Pars

1323

1327

[DPI Px Select], Par

1021

[Encoder Out Sel], or Par

430

[Resolver Spd Sel])

are set to the same value. See

Figure 87

on page

307

or Speed Reference Selection on

page

347

for a graphical representation of the drive's reference selections.

2. Both Pars

429

[Resolver Pos Sel] and

430

[Resolver Spd Sel] are non-zero.

3. More than one of the following parameters contains the same value:

786

[PID Source],

1204

[Line Spd Source], and

1284

[Ref Spd Source].

Spd Fdbk Err

1

With Par

478

[Spd Loss Flt Cfg] set to 1 “Alarm” an error condition associated with the

selected speed feedback device (analog tachometer, encoder, or resolver) was detected.

Spd Fdbk Loss

1

With Par

478

[Spd Loss Flt Cfg] set to 1 “Alarm”, the speed feedback device selected in Par

414

[Fdbk Device Type] is indicating less than 5% of Par

162

[Max Feedback Spd] while the

measured armature voltage is greater than the value of Par

455

[Spd FB Loss Lvl]. See the

“Spd Fdbk Loss” fault description on page

221

for more information.

Alarm

Type

Description

Start

Stop-

CF

Run Run Fwd Run Rev

Jog

1/2 Jog Fwd Jog Rev

Fwd/

Rev

Start
Stop-CF
Run
Run Fwd
Run Rev
Jog 1/2
Jog Fwd
Jog Rev
Fwd/Rev