Configure a Line Speed Signal

The line speed signal is the main reference for the speed or current regulator in
the follower drive(s).

In the Master drive:

Configure an analog output for the main speed reference (1 “Spd Ref
Out”)

In the Follower drive:

Set Par 80 [Anlg In3 Sel] to 12 “UserDefined0”

Set Par 786 [PID Source] to 19 “UsrDefined0” (Par 503).

In addition you can configure the following:

Enter the gain for the feed-forward signal in Par 787 [PID Source Gain]

Line Speed

Master

NIP-Roll

Reverse

Forward

Load Cell

0 - +10V

Tension Set

-10V

Set

Feedback

Line Speed Signal

Master

Drive

Slave
Drive

(Internal Ramp)

Line Speed Reference

+10V Forward

-10V Reverse

M

E

M

E