Supplemental Drive Information

Appendix A

DC Contactor Crimp Lug Kit
Specifications

Use the information provided in the table below to assist you in ordering the
correct Lug kit for your application.

C 495

495

404.4

300

HUBBELL_Y101W595GB

500

0.8

ABB_EHDB520C2P-1L2S

ABB_EHDB520C-1L22SS

(5)

667

667

544.9

400

HUBBELL_Y109W542GB

500

0.625

ABB_EHDB800C2P-1L2S

ABB_EHDB800C-1L22SS

(5)

D 800

830

678.1

500

(1)

500

0.463

ABB_EHDB960C2P-1L2S

ABB_EHDB960C-1L22SS

(5)

960

996

813.7

600

(2)

500

0.322

SIEMENS-MFG_14-193-
101-58-2 (Qty 2)

SIEMENS-MFG_14-193-
101-58-2 (Qty 1)

(5)

1K1

1162

949.4

700

(2)

500

0.322

SIEMENS-MFG_14-193-
101-58-2 (Qty 2)

SIEMENS-MFG_14-193-
101-58-2 (Qty 1)

(5)

1K3

1328

1085.0

800

(2)

500

0.255

CUTLER-
HAMMER_6702ED636-2
(Qty 2)

CUTLER-
HAMMER_6702ED636-2
(Qty 1)

(5)

1K4

1494

1220.6

900

(2)

500

0.255

CUTLER-
HAMMER_6702ED636-2
(Qty 2)

CUTLER-
HAMMER_6702ED636-2
(Qty 1)

(5)

(1) No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally.
(2) Coil voltage = 115V AC, 50/60Hz.
(3) See DC Contactor Crimp Lug Kit Specifications on page

259

for more information.

(4) Wire and Lug size dependant on enclosure dimensions and local codes.

Fram

e

Drive Current
Rating Code

DC
Amps

AC Line
Amps

Hp

Dynamic Brake Resistor
Kit Cat. No.

Armature
Voltage
(Volts)

Total DB
Resistance
(ohms)

DC Loop Contactor Cat. No.

(2)

DC Contactor
Crimp Lugs
Cat. No.

(3)

Drive without Dynamic
Brake

Drive with Dynamic
Brake

Rated Motor Armature

Current

(1)

A DC

DC Contactor Rating

A DC

Armature Conductor Size

(2)

AWG

DB Conductor Size

(3)

AWG

Armature Conductor

Crimp Lug Hole Size

DB Conductor Crimp

Lug Hole Size

Lug Kit Catalog

Number

4.1…35

56

8

8

#10

#10

1370-LG40

45…52

56

6

8

#10

#10

1370-LG52

55

56

4

8

#10

#10

1370-LG56

60…86

110

2

6

0.25 in.

0.25 in.

1370-LG92

100…110

110

1/0

4

0.25 in.

0.25 in.

1370-LG110

129

180

2/0

2

0.3125 in.

0.3125 in.

1370-LG140

146

180

3/0

2

0.3125 in.

0.3125 in.

1370-LG160

147…167

180

4/0

2

0.3125 in.

0.3125 in.

1370-LG180

207…218

280

300MCM

1/0

0.5 in.

0.375 in.

1370-LG228

250…265

280

400MCM

2/0

0.5 in.

0.375 in.

1370-LG268

266…280

280

500MCM

3/0

0.5 in.

0.375 in.

1370-LG280

(1) The Rated Motor Armature Current is taken directly from the motor nameplate or motor data. The current listed in this column is the maximum current allowed for the Armature Conductor Size (column

3) and the DC Contactor Rating (column 2).

(2) The armature conductors are sized by multiplying the Rated Motor Armature Current by 1.25 as provided for in NEC 420-22 (1987). The DC lug ratings are determined from NEC Table 310-16 (1987) for

copper conductors, insulation temperature rated at 75° C (167° F) at an ambient temperature of 30° C (86° F). If conditions are other than shown in NEC Table 310-16, then refer to application codes.

(3) The dynamic braking (DB) conductors are sized as in footnote 2 above, but at half ampacity due to the short time duration of current flow in these conductors, and has been sized to satisfy NEMA Standard

ICS 3-302.62 - Dynamic Braking. If the load inertia is larger than that of the motor, calculations must be made to determine correct conductor sizing and DB resistor wattage per NEMA Standard ICS 3-
302.62.