Chapter 1

Installation and Wiring

DC Analog Tachometer Terminal Block

Figure 62 - Analog Tachometer Terminal Block Location

See the PowerFlex Digital DC Drive Technical Data, publication

20P-TD001

,

for DC analog tachometer specifications.

Table 39 - DC Analog Tachometer Terminal Designations

Resolver Feedback Module

The resolver feedback module (catalog number 20P-RES-A0), which provides a
drive interface to a selection of compatible resolvers, must be ordered and
purchased separately from the drive. The resolver option module includes the
PowerFlex DC Drive Resolver Feedback Module Installation Instructions,
publication

20P-IN071

, which provides installation and wiring information. See

Resolver Type Selection on page

310

for more information on compatible

resolvers.

ATTENTION: The drive can overspeed if DIP switch S4 is set incorrectly, or the
tachometer is wired incorrectly. Failure to observe this precaution could result in
damage to, or destruction of, the equipment.

Label Signal

Description

Negative input

A

(Not Used)

B
C
+

Positive input
See Verify Motor Rotation and Run Feedback
Polarity Checks on page

103

for information

on determining feedback polarity.

22.7 / 45.4 / 90.7 / 181.6 / 302.9V

(1)

max voltage
8 mA max. current

(1) Maximum voltage depends on the configuration of DIP switch S4. See DC Analog Tachometer DIP Switch S4 Example on page

77

.

Analog Tachometer

terminal block

A

B

C

+