Figure 75, Fuses for non-regenerative frame c and d drives – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 247

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

247

Supplemental Drive Information

Appendix A

Figure 75 - Frame D Regenerative Drive - Leg Fuse Location

Fuses for Non-Regenerative Frame C and D Drives

AC input line and/or leg fuses are internally mounted and provided with frames
C and D drives. See Fuse Code FS4 in

Figure 71

on page

242

. Also, see

Figure 76

on page

249

for fuse locations.

Table 68 - AC Input Line Fuses - 230V AC Input Frame C Drives

Table 69 - Leg Fuses - 230V AC Input Frame D Drives

Table 70 - AC Input Line Fuses - 460V AC Input Frame C Drives

Leg fuses and switches are installed on the bus bars behind the control panel, which holds the circuit boards.

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC Line
Amps

Qty Bussmann

Mersen

SIBA

Square Body - Flush End Contact

C 521

521

426

3

170M5466 + switch 170H0069

6,9 URD 32 TTF 1000 + switch MS 3-V1-5 BS

20 671 32.1000 + switch 28 001 04

700

700

571

3

170M5466 + switch 170H0069

6,9 URD 32 TTF 1000 + switch MS 3V 1-5 BS

20 671 32.1000 + switch 28 001 04

Fram

e

Drive
Current
Rating
Code

DC
Amps

AC Line
Amps

Qty

Bussmann

Mersen

SIBA

Square Body - DIN 43653 Stud-Mount

D

875

875

715

6

170M6263 + switch 170H0069

Y300263 + switch MS 3V 1-5 UR

20 635 32.900 + switch 28 001 04

1K0

1050

858

6

170M6264 + switch 170H0069

Z300264 + switch MS 3V 1-5 UR

20 635 32.1000 + switch 28 001 04

Fr

am

e

Drive
Current
Rating
Code

DC
Amps

AC Line
Amps

Qty Bussmann

Mersen

SIBA

Square Body - Flush End Contact

C 495

495

404.4

3

170M5464 + switch 170H0069

6,9 URD 32 TTF 800 + switch MS 3-V1-5 BS

20 671 32.800 + switch 28 001 04

667

667

544.9

3

170M5466 + switch 170H0069

6,9 URD 32 TTF 1000 + switch MS 3-V1-5 BS

20 671 32.1000 + switch 28 001 04

Advertising
This manual is related to the following products: