Field Voltage Regulator Tuning Examples

Figure 98 - Field voltage oscillation

Oscillation after a speed change where [Arm Volt Kp] = 10% and [Arm Volt Ki]
= 80%.
Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage]

Figure 99 - Too small of a gain

The armature voltage increases where [Arm Volt Kp] = 3% and [Arm Volt Ki] =
5%.
Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage]

Figure 100 - Optimal field regulation

After a short transient, the field current and armature voltage are constant.
[Arm Volt Kp] = 40%, [Arm Volt Ki] = 5%.
Top: Par 234 [Fld Current Pct]
Bottom: Par 233 [Output Voltage]