Analog Input Configuration

The analog inputs default to ±10V. To configure the analog inputs for 0-10V, set
parameters [Anlg Inx Config] to 1, “0-10V”. To configure the analog inputs for a
current signal, set parameters [Anlg Inx Config] to 2, “0 - 20mA” or 3, “4 to
20mA”. In addition, switches S9, S10 and S11 must be properly configured (see
Control Circuit Board Jumper and DIP Switch Settings on page

76

for more

information).

Example 1:

The speed reference value of a drive is defined with an external voltage of 5V.
With this value the drive reaches the maximum allowable speed set in Par 45
[Max Ref Speed]. Enter a scaling factor of 2 in [Anlg In

x Scale] to scale the input

voltage from 5V to 10V.

Example 2:

An external analog reference reaches a maximum value of 9.8V. Enter a scaling
factor of 1.020 in [Anlg In

x Scale] to scale the maximum voltage from 9.8V to

10V.

The same result could be obtained via parameter [Anlg

x Tune Scale], by entering

the values of the appropriate parameters via the HIM. The maximum possible
analog input value (in this case 9.8V) must be present at the terminal with a
positive polarity at the time of configuration.

Σ

+

-

2

1

Volts

Ref_1-

Ref_1+

HW

input

type

Window comparator

F

From Digital Reference Setting

Anlg In1 Cmp

0

0 ms

Anlg In1 Cmp Eq

Anlg In1 Cmp Dly

Anlg In1 Cmp Er

0

+/-10V

Anlg In1 Config

1

Ain1 Tune Scale

0

Anlg In1 Offset

1

Anlg In1 Scale

0

Anlg In1 Tune

0 ms

Anlg In 1 Filter

0

Anlg In1 Target

Speed Ref A

Anlg In1 Sel

Analog Input 1

See the “Analog Inputs / Outputs & Mapping” block diagram on page

346

for more information.