Chapter 3

Programming and Parameters

DYNAMIC C

O

NTROL

Lo

ad Limits

699

[Enable Droop]
Enables/Disables the Droop function.
“Enabled” = The Droop function is enabled.
“Disabled” = The Droop function is disabled.
Note: This parameter can be assigned to a digital input.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

700

[Droop Limit]
The speed reference correction range within which the droop function becomes
active.
Note: See Droop Compensation on page

285

for more information.

Default:

Min/Max:
Units:

1750

0 / Par 45 [Max Ref Speed]
rpm

16-bit
Int

715

[Torq Limit Type]
This parameter determines the response of the drive during a current limiting
condition.
“T Lim PosNeg” = The active positive torque limit is set by the value defined in

Par 7 [Current Limit] and the active negative torque limit is set by the value
defined in Par 9 [Current Lim Neg].

“T Lim MtrGen” = With this option the following three conditions apply:

1. If the motor speed is greater than +1% of Par 162 [Max Feedback Spd], the

active positive torque limit is set by the value defined in Par 8 [Current Lim
Pos] and the active negative torque limit is set by the value defined in Par 9
[Current Lim Neg].

2. If the motor speed is less than –1% of Par 162 [Max Feedback Spd] the

active positive torque limit is set by the value defined in Par 9 [Current Lim
Neg] and the active negative torque limit is set by the value defined in Par 8
[Current Lim Pos].

3. If the motor speed is greater than –1% of Par 162 [Max Feedback Spd] and

less than +1% of Par 162 [Max Feedback Spd] the active positive and
negative torque limits are set by the value defined in Par 8 [Current Lim Pos].

Note: The option names were corrected to those shown above for firmware version
4.001.

Default:

Options:

0 =

0 =
1 =

“T Lim PosNeg”

“T Lim PosNeg”
“T Lim MtrGen”

16-bit
Int

7,
8,
9,
162

St

op

M

od

es

38

[Fast Stop Time]
The amount of time to decelerate the drive to a complete stop and disable the
drive. The deceleration rate for Fast stop = [Maximum Speed] / [Fast Stop Time].
This feature can be used when [Digital Inx Sel] is set to 30 “Fast Stop” or when
certain alarms are configured for “Fast Stop”. See Pars 354 [Aux Inp Flt Cfg] and 365
[OverTemp Flt Cfg].

Default:

Min/Max:
Units:

10

0 / 65535
s

16-bit
Int

354,
365

627

[Spd 0 Trip Delay]
The amount of time that will elapse after the drive reaches zero speed before it is
disabled.

Default:

Min/Max:
Units:

0

0 / 40000
ms

16-bit
Int

1262 [Closing Speed]

Motor speed at which the brake is closed. Used with External Brake Control.

Default:

Min/Max:
Units:

30

0 / 200
rpm

16-bit
Int

1263 [Opening Delay]

Amount of time before the brake will open after the drive has been enabled. Used
with External Brake Control.

Default:

Min/Max:
Units:

0

0 / 30000
ms

16-bit
Int

1265 [Ramp In Zero En]

Enables/Disables the setting of the ramp input to zero. Used with External Brake
Control.

Default:

Options:

0 =

0 =
1 =

“Disabled”

“Disabled”
“Enabled”

16-bit
Int

1266 [Actuator Delay]

Amount of time before the actuator releases the load. Used with External Brake
Control.

Default:

Min/Max:
Units:

0

0 / 30000
ms

16-bit
Int

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

A

A

A