Communication configurations, Typical programmable controller configurations, Logic command/status words – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 234

Advertising
background image

234

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Appendix A

Supplemental Drive Information

Communication
Configurations

Typical Programmable Controller Configurations

Logic Command/Status Words

See parameter

1328

[Drive Logic Rslt] for more information.

Figure 66 - Logic Command Word

IMPORTANT

If block transfers are programmed to continuously write information to the
drive, care must be taken to properly format the block transfer. If attribute 10 is
selected for the block transfer, values will be written only to RAM and will not
be saved by the drive. This is the preferred attribute for continuous transfers. If
attribute 9 is selected, each program scan will complete a write to the drives
non-volatile memory (EEprom). Because the EEprom has a fixed number of
allowed writes, continuous block transfers will quickly damage the EEprom. Do
Not assign attribute 9 to continuous block transfers. Refer to the individual
communication adapter User Manual for additional details.

Logic Bits

Command

Description

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

x Stop

(1)

0 = Not Stop
1 = Stop

x

Start

(1)(2)

(1) A “0 = Not Stop” condition (logic 0) must first be present before a “1 = Start” condition will start the drive. The Start command acts

as a momentary Start command. A “1” will start the drive, but returning to “0” will not stop the drive.

(2) This Start will not function if a digital input (parameters 133…144) is programmed for 2-Wire Control (option 5 “Run”, 6 “Run

Forward” or 7 “Run Reverse”).

0 = Not Start
1 = Start

x

Jog

0 = Not Jog
1 = Jog

x

Clear Faults

0 = Not Clear Faults
1 = Clear Faults

x x

Direction

00 = No Command
01 = Forward Command
10 = Reverse Command
11 = Hold Present Direction

x

Local Control 0 = No Local Control

1 = Local Control

x

MOP
Increment

0 = Not Increment
1 = Increment

x x

Accel Rate

00 = No Command
01 = Use Accel Time 1
10 = Use Accel Time 2
11 = Use Present Time

x

x

Decel Rate

00 = No Command
01 = Use Decel Time 1
10 = Use Decel Time 2
11 = Use Present Time

x

x

x

Reference
Select

(3)

(3) This Reference Select will not function if a digital input (parameters 133…144) is programmed for “Speed Sel 1, 2 or 3” (option 17,

18 or 19). Note that Reference Selection is “Exclusive Ownership”. See [Reference Owner] on page

188

.

000 = No Command
001 = Ref. 1 (Spd Ref A)
010 = Ref. 2 (Spd Ref B)
011 = Ref. 3 (Preset Spd 3)
100 = Ref. 4 (Preset Spd 4)
101 = Ref. 5 (Preset Spd 5)
110 = Ref. 6 (Preset Spd 6)
111 = Ref. 7 (Preset Spd 7)

x

MOP
Decrement

0 = Not Decrement
1 = Decrement