Installation and Wiring

Chapter 1

Output power wiring to the motor must employ cable with a braided
shield providing 75% or greater coverage, or the cables must be housed in
metal conduit, or equivalent shielding must be provided. Continuous
shielding must be provided from the drive enclosure to the motor
enclosure. Both ends of the motor cable shield (or conduit) must terminate
with a low-impedance connection to earth.

At the motor end, the motor cable shield or conduit must terminate in a
shielded connector that must be properly installed in an earthed motor
wiring box attached to the motor. The motor wiring box cover must be
installed and earthed.

All control (I/O) and signal wiring to the drive must use cable with a
braided shield providing 75% or greater coverage, or the cables must be
housed in metal conduit, or equivalent shielding must be provided. When
shielded cable is used, terminate only the drive end of the cable shield to
earth with a low-impedance connection.

Motor cabling must be separated from control and signal wiring wherever
possible.

Maximum motor cable length must not exceed the maximum length
indicated in the table on

page 40

for compliance with radio frequency

emission limits for the specific standard and installation environment.

Pollution Degree Ratings According to EN 61800-5-1

IMPORTANT

Use of EMC filters other than those listed in

Table 9

on page

page 40

must be

verified in the application. Additional filters are listed in Alternate EMC Filters
on page

261

.

Pollution
Degree

Description

1

No pollution or only dry, non-conductive pollution occurs. The pollution has no influence.

2

Normally, only non-conductive pollution occurs. Occasionally, however, a temporary conductivity caused
by condensation is to be expected, when the drive is out of operation.

3

Conductive pollution or dry non-conductive pollution occurs, which becomes conductive due to
condensation, which is to be expected.

4

The pollution generates persistent conductivity caused, for example by conductive dust or rain or snow.