Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

Chapter 3

Programming and Parameters

D

YNAMIC C

O

NTROL

Adapt

v Re

gu

lator

187

[Adaptive Joint 2]
Defines a range above and below the value set in Par 185 [Adaptive Spd 2] with in
which there is a linear change in gain from parameter set 2 to parameter set 3 to
prevent jumps in the adaptive speed regulator. The value in this parameter is
defined as percentage of the value defined Par 45 [Max Ref Speed].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

6.11

0.00 / 200.00
%

Real

185

188

[Adaptive P Gain1]
Proportional gain for the range from zero to the value set in Par 184 [Adaptive Spd
1]. The value in this parameter is defined as percentage of the value defined in Par
93 [Spd Reg Kp Base].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

10.00

0.00 / 100.00
%

Real

93,
184

189

[Adaptive I Gain1]
Integral gain for the range from zero to Par 184 [Adaptive Spd 1]. The value in this
parameter is defined as percentage of the value defined Par 94 [Spd Reg Ki Base].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

1.00

0.00 / 100.00
%

Real

94,
184

190

[Adaptive P Gain2]
Proportional gain for the range of values defined beginning with the value of Par
184 [Adaptive Spd 1] to the value defined in Par 185 [Adaptive Spd 2]. The value in
this parameter is defined as percentage of the value defined Par 93 [Spd Reg Kp
Base].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

10.00

0.00 / 100.00
%

Real

93,
184,
185

191

[Adaptive I Gain2]
Integral gain for the range of values defined beginning with the value of Par 184
[Adaptive Spd 1] to the value defined in Par 185 [Adaptive Spd 2]. The value in this
parameter is defined as percentage of the value defined Par 94 [Spd Reg Ki Base].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

1.00

0.00 / 100.00
%

Real

94,
184,
185

192

[Adaptive P Gain3]
Proportional gain for the range of values beginning above the value defined in Par
185 [Adaptive Spd 2]. The value in this parameter is defined as percentage of the
value defined Par 93 [Spd Reg Kp Base].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

10.00

0.00 / 100.00
%

Real

93,
185

193

[Adaptive I Gain3]
Integral gain for the range of values beginning above the value defined in Par 185
[Adaptive Spd 2]. The value in this parameter is defined as percentage of the value
defined Par 94 [Spd Reg Ki Base].
Note: See Adaptive Speed Regulator on page

317

for more information.

Default:

Min/Max:
Units:

1.00

0.00 / 100.00
%

Real

94,
185

Fil

e

Gr

oup

No

.

Parameter Name & Description

See

page 114

for symbol descriptions

Values

Da

ta

T

yp

e

Rela

ted

A

A

A

A

A

A

A

Advertising