The motor reaches maximum speed immediately, Testpoint codes and functions, The testpoint codes and functions table – Rockwell Automation 23P PowerFlex Digital DC Drive User Manual

Page 229

Advertising
background image

Rockwell Automation Publication 20P-UM001K-EN-P - July 2014

229

Troubleshooting

Chapter 4

The motor reaches maximum speed immediately

Testpoint Codes and
Functions

Select a testpoint with Par

1381

[TestPoint Sel]. Values can be viewed with Par

1382

[TestPoint Data].

Drive Symptom

Action

The motor accelerates to maximum speed and cannot be
controlled.

Check the analog input voltage and speed reference values:
Parameters 1404 [Analog In1 Value], 1405 [Analog In2 Value], 44 [Speed Ref A] and 48 [Speed Ref B]
Check the setting of switch S9 and parameter 71 [Anlg In1 Config], S10 and 76 [Anlg In2 Config] or S11 and 81

[Anlg In3 Config].

The feedback device, encoder, resolver, or DC analog tachometer is not connected/configured, incorrectly connected
or has failed.
Change parameter 414 [Fdbk Device Type] to 3 “Armature” to test the encoder or DC analog tachometer feedback.

No.

(1)

(1) Enter in [TestPoint Sel].

Description

Values
Minimum

Maximum

Default

566

Rx count

0

65535

0

567

Tx count

568

BusLoss count

569

Port 1 Timeout

570

Port 2 Timeout

571

Port 3 Timeout

572

Port 4 Timeout

573

Port 5 Timeout

574

Port 6 Timeout

575

Internal gain of P188 (x100)

576

Internal gain of P189 (x100)

577

Internal gain of P190 (x100)

578

Internal gain of P191 (x100)

579

Internal gain of P192 (x100)

580

Internal gain of P193 (x100)

Advertising
This manual is related to the following products: